General - Operating Mode After Reset - ABB SmartTouch B/stainless Product Manual

Table of Contents

Advertisement

Heating: For operating a heat-based single-room control. The temperature is regulated to
the setpoint value defined in the parameter. The "Controller type" and "Heating type" can be
programmed for optimal control.
Heating with additional stage: In addition to the control function described under heating, the
additional stage enables the activation of an additional heating circuit. This type of additional
stage is used, for example, to quickly heat up a bathroom with floor heating via a heated
towel rack.
Cooling: For operating a cooling-based single-room control. The temperature is regulated to
the setpoint value defined in the parameter. The "Controller type" and "Cooling type" can be
programmed for optimal control.
Cooling with additional stage: In addition to the control function described under cooling, the
additional stage enables the activation of an additional cooling device. This type of
additional stage is used, for example, to quickly cool a room via an added cooling device.
Heating and cooling: For operating a two-wire or four-wire system used to heat or cool a
room. Switching between heating and cooling takes place using a central switch (two-wire
system) or is carried out manually and / or automatically via the single room temperature
controller (four-wire system).
Heating and cooling with an additional stage: In addition to the heating and cooling
functions, one additional stage each with an autonomous controller type can be
programmed.

10.24.2 General - Operating mode after reset

Options:
After a reset the device will run in the operating mode after a restart until a new operating mode
is set as the result of device operation or by communication objects, as the case may be. This
operating mode should be defined during the planning phase. An improperly defined operating
mode can result in a loss of comfort or increased energy consumption.
Comfort: If the room temperature is not automatically lowered and the room is therefore
controlled independent of its use.
Standby: If the room is controlled automatically, e.g. by a presence detector, as a function of
its use.
Eco mode: If the room is controlled automatically or manually as a function of its use.
Frost/heat protection: If only the building protection function is necessary in the room after a
reset.
Product manual 2CKA001473B5343
KNX control elements and application parameters
Heating with additional stage
Cool
Cooling with additional stage
Heating and cooling
Heating and cooling with additional stage
Comfort
Standby
Eco mode
Frost/heat protection
Application "Internal RTC"
│228

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents