Setpoint Adjustment - Setpoint Adjustment Master/Slave Via Communication Object; Setpoint Adjustment - Resetting Of The Manual Adjustment For Receipt Of A Basic Setpoint; Setpoint Adjustment - Resetting The Manual Adjustment For Change Of Operating Mode; Setpoint Adjustment - Resetting The Manual Adjustment Via Object - ABB SmartTouch B/stainless Product Manual

Table of Contents

Advertisement

This parameter is used to specify the step size for manual setpoint adjustment.

10.24.99 Setpoint adjustment - Setpoint adjustment master/slave via communication object

Options:
This parameter is used to specify whether the setpoint adjustment for master/slave is carried
out via a temperature value or a 1-byte counter value.
10.24.100
Setpoint adjustment — Resetting of the manual adjustment for receipt of a basic
setpoint
Options:
Activating this parameter will cause the manual adjustment to be deleted and the new setpoint
value to be provided when a new value is received via the "Basic setpoint" object.
If the parameter is deactivated, the manual adjustment is added to the new base setpoint value.
Example: Previous base setpoint value of 21°C + manual adjustment of 1.5°C = 22.5°C. The
object receives a new basic setpoint of 18°C plus the previous manual adjustment of 1.5°C for a
total of 19.5°C.
10.24.101
Setpoint adjustment — Resetting the manual adjustment for change of operating
mode
Options:
If the device switches to a new operating mode, the manual adjustment is deleted and the
parameterised setpoint temperature for the operating mode plus any change by the base
setpoint value object will be applied if this parameter is activated. Example: Comfort
temperature of 21°C plus manual adjustment of 1.5°C = 22.5°C. Change to Eco with
programmed temperature 17°C. The device regulates the temperature to 17°C, since the
manual adjustment is deleted.
If the parameter is deactivated, the manual setpoint adjustment will be added to the temperature
in the new operating mode. Example: Comfort temperature of 21°C plus manual adjustment of
1.5°C = 22.5°C. If the system switches to Eco with a parameterised temperature of 17°C, the
device regulates the temperature to 18.5°C, since the manual adjustment is added.
10.24.102
Setpoint adjustment — Resetting the manual adjustment via object
Options:
Product manual 2CKA001473B5343
KNX control elements and application parameters
0.5°C
1.0°C
1-byte counter value
Relative temperature value
Absolute temperature value
Deactivated
Activated
Deactivated
Activated
Deactivated
Application "Internal RTC"
│263

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents