Setpoint Settings - Increase For Cooling Standby By; Setpoint Settings - Setpoint For Cooling Economy; Setpoint Settings - Increase For Cooling Economy; Setpoint Settings - Setpoint For Cooling Building Protection - ABB SmartTouch B/stainless Product Manual

Table of Contents

Advertisement

Notice
This parameter is only available when the "Control function" parameter is set on
"Cooling" or "Cooling with additional stage" and parameter "Setpoint heating
comfort = setpoint cooling comfort" is set on "deactivated".
10.24.83 Setpoint settings — Increase for cooling standby by
Options:
Specifies the temperature in cooling mode when nobody is present. On devices with a display,
this mode is indicated by the standby icon.
Notice
This parameter is only available when the "Control function" parameter is set on
"Cooling", "Cooling with additional stage", "Heating and cooling" or "Heating and
cooling with additional stages" and parameter "Setpoint for standby and Eco are
absolute values" is set on "deactivated".
10.24.84 Setpoint settings — Setpoint for cooling economy
Options:
Specifies the comfort temperature for cooling economy.
Notice
This parameter is only available when the "Control function" parameter is set on
"Cooling" or "Cooling with additional stage" and parameter "Setpoint heating
comfort = setpoint cooling comfort" is set on "deactivated".
10.24.85 Setpoint settings — Increase for cooling economy
Options:
Specifies the temperature in cooling mode when nobody is present. On devices with a display,
this mode is indicated by the Eco icon.
Notice
This parameter is only available when the "Control function" parameter is set on
"Cooling", "Cooling with additional stage", "Heating and cooling" or "Heating and
cooling with additional stages" and parameter "Setpoint for standby and Eco are
absolute values" is set on "deactivated".
10.24.86 Setpoint settings — Setpoint for cooling building protection
Options:
Function for protecting the building against heat. On devices with a display, this mode is
indicated by the heat protection icon. Manual operation is blocked.
Product manual 2CKA001473B5343
KNX control elements and application parameters
Setting option between 0 - 15
Setting option between 10 - 40
Setting option between 0 - 15
Setting option between 27 - 45
Application "Internal RTC"
│259