Typical values for summer compensation are:
20°C: lower outside temperature value
■
32°C: upper outside temperature value
■
0 K: lower setpoint offset
■
4 K: upper setpoint offset
■
That means that a flowing setpoint increase of 0 to 4 K occurs if the outside temperature
increases from 20°C to 32°C.
Notice
This parameter is only available if the "Summer compensation" parameter is set
on "Yes".