Summer Compensation - Offset Of The Setpoint Temperature For The Entry Into Summer Compensation; Summer Compensation - (Upper) Exit Temperature For Summer Compensation; Summer Compensation - Offset Of The Setpoint Temperature For The Exit From Summer Compensation - ABB SmartTouch B/stainless Product Manual

Table of Contents

Advertisement

Options:
The parameter is used to specify the lower outside temperature value up to which temperature
value the setpoint correction (summer compensation) is performed based on too high an
outside temperature.
Notice
This parameter is only available if the "Summer compensation" parameter is set
on "Yes".
10.24.134
Summer compensation - Offset of the setpoint temperature for the entry into
summer compensation
Options:
The parameter is used to specify how many degrees Kelvin the setpoint value will be increased
by during summer compensation when the lower temperature value is reached.
Typical values for summer compensation are:
20°C: lower outside temperature value
32°C: upper outside temperature value
0 K: lower setpoint offset
4 K: upper setpoint offset
That means that a flowing setpoint increase of 0 to 4 K occurs if the outside temperature
increases from 20°C to 32°C.
Notice
This parameter is only available if the "Summer compensation" parameter is set
on "Yes".
10.24.135

Summer compensation - (Upper) exit temperature for summer compensation

Options:
The parameter is used to specify the upper outside temperature value up to which temperature
value the setpoint correction (summer compensation) is performed based on too high an
outside temperature.
Notice
This parameter is only available if the "Summer compensation" parameter is set
on "Yes".
10.24.136
Summer compensation - Offset of the setpoint temperature for the exit from
summer compensation
Options:
The parameter is used to specify how many degrees Kelvin the setpoint value will be increased
by during summer compensation when the upper temperature value is reached.
Product manual 2CKA001473B5343
KNX control elements and application parameters
Setting option between 10 - 40
Setting option between 0 - 25
Setting option between 10 - 40
Setting option between 0 - 25
Application "Internal RTC"