Additional Heating Stage - Hysteresis - ABB SmartTouch B/stainless Product Manual

Table of Contents

Advertisement

10.24.31 Additional heating stage - Hysteresis

Options:
The hysteresis of the two-point controller specifies the fluctuation range of the controller around
the setpoint value. The lower switching point is located at "Setpoint value minus hysteresis" and
the upper point is at "Setpoint value plus hysteresis".
Notice
This parameter is only available when the "Control value type" parameter is set
either on "2-point 1 Bit, Off/On" or "2-point 1 Byte, 0/100%".
Product manual 2CKA001473B5343
KNX control elements and application parameters
Setting option between 0.3 - 25
Application "Internal RTC"
│241

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents