Setpoint Adjustment; Setpoint Adjustment - Maximum Manual Increase During Heating Mode (0 - 9°C); Setpoint Adjustment - Maximum Manual Reduction During Heating Mode (0 - 9°C); Setpoint Adjustment - Maximum Manual Increase During Cooling Mode (0 - 9°C) - ABB SmartTouch B/stainless Product Manual

Table of Contents

Advertisement

10.24.93 Setpoint adjustment

10.24.94 Setpoint adjustment — Maximum manual increase during heating mode (0 - 9°C)
Options:
This preset can be used to limit the manual increase during heating.
Note
This parameter is only available when parameter "Controller function" is set
on "Heating" and parameter "Control value type" on "2-point 1 bit, On/Off" or
"2-point 1 byte, 0/100%".
10.24.95 Setpoint adjustment — Maximum manual reduction during heating mode (0 - 9°C)
Options:
This preset can be used to limit the manual decrease during heating.
Note
This parameter is only available when parameter "Controller function" is set
on "Heating" and parameter "Control value type" on "2-point 1 bit, On/Off" or
"2-point 1 byte, 0/100%".
10.24.96 Setpoint adjustment — Maximum manual increase during cooling mode (0 - 9°C)
Options:
This preset can be used to limit the manual increase during cooling.
Note
This parameter is only available when the "Control function" parameter is set on
"Cooling," "Cooling with additional stage," "Heating and cooling" or "Heating and
cooling with additional stages".
10.24.97 Setpoint adjustment — Maximum manual reduction during cooling mode (0 - 9°C)
Options:
This preset can be used to limit the manual decrease during cooling.
Note
This parameter is only available when the "Control function" parameter is set on
"Cooling," "Cooling with additional stage," "Heating and cooling" or "Heating and
cooling with additional stages".

10.24.98 Setpoint adjustment - Step size of manual setpoint adjustment

Options:
Product manual 2CKA001473B5343
KNX control elements and application parameters
Setting option between 0 - 9
Setting option between 0 - 9
Setting option between 0 - 9
Setting option between 0 - 9
0.1°C
0.2°C
Application "Internal RTC"
│262

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents