IEC 60870-5-103 communication.
Signal name / signal description
The Data ID† (say, signal number) showing the status of the frame is set from the signal
list in the IED. If the setting value (signal No.) is "0", all setting items related events are
disable and the frame is not provided.
†Note: A relevant Data ID is required to select; the description is obtained
automatically.
Type ID
Type ID=1 (Time-tagged message) or Type ID=2 (Time-tagged message with relative time)
is selected to set the frame type. It is recommended that the frame related to status is set
to Type ID=1 and the frame related to faults is set to Type ID=2. In Type ID=2, the trigger
signal for the relative time should be set. For the setting, see Section 11.5.6(i).
INF
Information number (INF) of the frame is set. The INF can be set to 0 to 255. When the
standard frame is provided, the INF according to the Appendix† is recommended. If the
frame out of standard is provided, the INF should be set referring Table 11.5-5 and the
Appendix†.
Table 11.5-5
Appendix: IEC 60870-5-103 interoperability: Semantics of Information
†Note: See
number
(→page 1118).
FUN
Function type (FUN) is set referring to Table 11.5-6. The FUN can be set to 0 to 255. When
clicking the "Change all FUNs" on the Common setting screen, all FUNs are changed to the
setting values at Common setting.
Table 11.5-6
INF category of Monitor direction
INF
0 to 15
system functions
16 to 31
Status
32 to 47
Supervision
48 to 63
earth fault
64 to 127
short circuit
128 to 143
auto-reclosure
144 to 159
Measurands
160 to 239
not used
240 to 255
generic functions
Semantics of Function type
0 - 127
private range
128
distance protection
129
not used
144
not used
145
not used
160
overcurrent protection
161
not used