Toshiba GR-200-5 Instruction Manual page 703

Multi functional protection ied

Advertisement

Function key logic for F1
(Function ID: 240001)
"FUNC-KEY1"
(
240001_
Pressing the F1 key
F1
Setting Data ID
(
240001_
"BO1_SOURCE"
for the [Signal]†
Instant
[Logic]
Toggle
‡Note: The BO1 circuit is used just for an explanation; it is discussed in Chapter
Technical description: Binary IO module
†Note: When the user wishes that the signal can enter at "BO1-SOURCE (200B41
31200E11D in IO_SLOT1)", set the BO1-SOURCE (200B41 31200E11D) for the
setting [Signal] of the F1 key. Note that, set Off for the scheme switch [BO1_CPL]
The user can select either Toggle or Instant modes for the signal generation using scheme
switch [LOGIC], as shown in Table 5.7-5. Thus, the user can substitute "F1-SIGNAL (240001
310001737)" for the "FUNC-KEY1 SIGNAL (240001 310001730)", provided the Toggle mode
is preferred. FUNC-KEY2 to FUNC-KEY7 are also shown in Table 5.7-7.
Table 5.7-5 Signal mode selection using setting [LOGIC]
Setting
Toggle
Instant
Setting Data ID "F1
SIGNAL" for the
[Input signal 1]
3100001730)
&
"F1 signal"
3100001737)
&
Figure 5.7-4 F1 key connected with the BO1‡
Generated signal corresponding to pressing the function key
Pressing Key
Binary signal
Pressing Key
Binary signal
BO1 circuit at IO_SLOT1 (Function ID: 200B01)
Signal designated by
≥1
setting [Input signal 1]
[Input signal 2]
[Input signal 3]
[Input signal 4]
[Input signal 5]
[Input signal 6]
[Input signal 7]
[Input signal 8]
PLC connection point in BO1
200B01 310200E11D
BO1_SOURCE
(see Chap. 5.6).
- 683 -
6F2T0207 (0.01)
"
"
BO1
(
200B01_8002001112)
DRIVER
&
≥1
"
BO1-RB
On
&
[BO1_CPL]
(200B01_8002001113)
Off
To contact health
check
GRE200 (5,6)
Terminal and
wire
Signal to the
device
BO1
"

Advertisement

loading