Toshiba GR-200-5 Instruction Manual page 492

Multi functional protection ied

Advertisement

Figure 4.1-49 shows a setting example for the 43SW scheme. Select and operate commands
drive the BO1 to BO4 contacts. To check that the contact health check function is working
correctly, the respective points of the BO-RBs should be connected as shown in Table 4.1-30, to
demonstrate that the settings are physically matched with the BO contacts.
Example #1
"DPSY01_OSL_BO_FLG" is connected to "BO1" at IO#1
"DPSY01_FSL_BO_FLG" is connected to "BO2" at IO#1
"DPSY01_OEX_BO_CSF" is connected to "BO3" at IO#1
"DPSY01_FEX_BO_CSF" is connected to "BO4" at IO#1
Remote/Local-end
"
DPSY01_OSL_BO_FLG
(511001 8602011DC6)
Select-Closing
command
"
DPSY01_FSL_BO_FLG
(511001 8A02011DC4)
Select-Open
command
"
DPSY01_OEX_BO
(511001 8202011DD3)
Operate-Closing
command
"
DPSY01_FEX_BO
(511001 8102011DD0)
Operate-Open
command
Figure 4.1-49 Contact health check setting and 43SW diagram for example #1
Setting for the contact health check (normal setting, example)
Table 4.1-30 Setting example for contact health check
"
"
BO1-RB
(
200B41_8002001113)
"
"
BO2-RB
(
200B41_8102011113)
"
"
BO3-RB
(
200B41_8202021113)
"
"
BO4-RB
(
200B41_8302031113)
Contact health check settings for example #1
[DPSY01-OSLBORD] =" 200B418002001113"(BO1-RB)
[DPSY01-FSLBORD]=" 200B418102011113" (BO2-RB)
[DPSY01-OEXBORD]=" 200B418202021113" (BO3-RB)
[DPSY01-OEXBORD]=" 200B418302031113" (BO4-RB)
BIO module
Drivers
SW1 is driven with
BO1 at IO#1
BO1
"
SW2 is driven with
BO2 at IO#1
BO2
"
SW3 is driven with
BO3 at IO#1
BO3
"
SW4 is driven with
BO4 at IO#1
BO4
"
- 472 -
6F2T0207 (0.01)
43SW
Plus (+)
SW 1
Closing
SW 3
SW 2
SW 4
Open
Minus (−)
GRE200 (5,6)
OK
OK
OK
OK