Scheme logic
2.23.3
Trip-command collection
(i)
Trip-command grouping gathers the trip signals provided by each protection function and
groups them to the trip operation commands "OPT-TRIP", "OPT-TRIP-A", "OPT-TRIP-B", and
"OPT-TRIP-C" for trip-signal generation, as shown in Figure 2.23-2.
The TRC logic has PLC connection points, which the user can program for issuing the
trip command. For example, if the user wishes to trip the CB using signals generated by
external relays, the signals can be connected to the TRC logic using the following PLC
connection points: TRIP-A_ADD, TRIP-B_ADD, TRIP-C_ADD and TRIP_ADD.
Figure 2.23-2 Scheme logic for Trip-command collection
Fault identifier for relay element operated in each phase
FC*_OPT_
FC*_OPT_
AR
Phase-A
Phase-B
N.A.
N.A.
X
X
N.A.
N.A.
Protection
FC*-OPT-TRIP_A
functions
FC01
FC02
FC*-OPT-TRIP_B
FC40
FC*-OPT-TRIP_C
FC*-OPT-TRIP
FC*_OPT_
FC*_OPT_
BR
CR
Phase-C
Phase-AB
N.A.
N.A.
≥1
800000EBB3 TRIP-A_ADD
≥1
810000EBB4 TRIP-B_ADD
≥1
820000EBB5 TRIP-C_ADD
≥1
830000EBB6 TRIP_ADD
- 264 -
6F2T0207 (0.01)
FC*_OPT_
ABR
BCR
Phase-BC
N.A.
N.A.
N.A.
N.A.
8000001B60
OPT-TRIP-A
8100001B61
OPT-TRIP-B
8200001B62
OPT-TRIP-C
8300001B63
OPT-TRIP
GRE200 (5,6)
FC*_OPT_
CAR
Phase-CA
N.A.
N.A.

Advertisement

loading

This manual is also suitable for:

Gr-200 seriesGr-200-6