[Type3] Mapping about Input register type
Figure 11.4-24 illustrates a mapping example for the Modbus Input register. In the figure, a
signal (Data ID) of the TCPIP_DRV function are mapped for the Modbus address
Modbus screen in Simple mode
The Input register type is Read-Only mode.
Modbus address: 10000
IED Data ID (FID: 230201)
2
3110101001
RX1_CNT
Data length of the RX1_CNT is 16-bits type.
Signal monitoring point (Data ID)
Figure 11.4-24 Example setting of Modbus Input register
Note: Addresses from 10000 —10999 are designed for 8-bits or 16-bits data length (see
2
Table 11.4-2).
Read Input register
- 937 -
Dropped
IED output point
Dragged
IED signals (Data IDs)
6F2T0207 (0.01)
(10000).
1
GRE200 (5,6)