Toshiba GR-200-5 Instruction Manual page 885

Multi functional protection ied

Advertisement

LAN operation
LAN address (IP address)
11.2.1
The IED can have the communication with "Transmission Control Protocol/Internet Protocol
(TCP/IP)". The user can set the information about IP addresses and other TCP/IP. Table 11.2-1
shows the setting items provided for the LAN†.
These setting values have been included in the CID file of the IEC61850. When the IED starts
up and if values except for the 0.0.0.0 values or default are set in the CID file, the CID
information is taken into the IED.
As the setting values have been included in the CID file, the user can define these values with
the engineering tool (GR-TIEMS). If the user wishes to modify those and the IEC61850 is used
to communicate, the user can change those with the GR-TIEMS. The user is required to write
both of setting values and IEC61850-CID file into the IED.
Ports
Setting items
IPADDRESS1
LANs at
C1 & C2
SUBNETMASK1
GATEWAY1
(PortA&B)
When wishing to change addresses, enter the new LAN with LAN setting sub-menu. Figure
11.2-1 shows the setting menu provided to change the addresses‡.
Figure 11.2-1 Local LAN setting menu (on IED screen)
†Note: For the LAN communication modules, see Chapter
processing and communication module
‡Note: IP address has to be assigned for both C1 and C2.
‡Note: Chapter
address in the IED using the LCD screen.
Table 11.2-1 TCP/IP settings at LAN modules
Range
0.0.0.0–255.255.255.255
0.0.0.0–255.255.255.255
0.0.0.0–255.255.255.255
LAN
10:48
IPADDRESS1
192.168.1.11
SUBNETMASK1
255.255.255.1
GATEWAY1
192.168.1.1
User interface: Setting sub-menu
- 865 -
Setting meaning
First IP address
Subnet mask
Default gateway
1/6
+
+
+
Technical description: Signal
(→p. 645).
(→p. 997) describes how to set the
6F2T0207 (0.01)
Default value
192.l68.1.11
255.255.255.0
192.168.1.1
GRE200 (5,6)