Multi functional protection ied

Advertisement

Event recorder
Signals will be generated when something are happening in the IED; they are called event
information. If wishing to record them, the user should select signals for the event recorder
function. There are 768 triggers, some of which have been set as a default, in the function.
Three categories are provided for the triggers; hence, it is possible that the user can group the
events depending on the degrees, such as errors, operations, and elements, etc. Additionally,
event detection methods are published for the user in the function, so the user can define the
event recording rules with settings. The function can recorded it in a millisecond accuracy; the
information will stay in the memory until 1024 events are recorded. After that, the oldest one
will be deleted if a new one appears.
Trigger signals
8.2.1
The event is memorized when the event recorder detects changing the trigger signal that is
connected with the logic signal; they are defined using settings [Trigger ID1] to [Trigger ID768].
Settings [End of E.Record-1] and [End of E.Record-2] are provided for grouping†; the user can
adjust the size of the 'Event Record1' group using the [End of E.Record-1]. The next 'Event
Record2' group is set with the [End of E.Record-2]. The remains are set for the 'Event Record3'
group. Remember that the [Trigger ID1] etc. are required to set together with the [Event
Name1] etc.; preferred names by the user should be less than 18 letters.
Setting [End of E.Record-1] = 256
Setting [End of E.Record-2] = 512
3000001001
FR_CLR
FAULT RECORD (200602)
Setting [Trigger ID14]
= 200602 3000001001
Setting [Trigger Mode14]
= On
Setting [Event Name14]
= F.Record clear
3010001001
SYS_CHG
Setting_PF (201400)
Setting [Trigger ID7]
= 201400 3010001001
Setting [Trigger Mode7] = Change
Setting [Event Name7]
= Set group change
Figure 8.2-1 Relation between function signals and triggers for Event record1
Figure 8.2-1 illustrates signals connected with triggers in the event recorder. For example,
'SYS_CHG' is connected with trigger#7 using the [Trigger ID7] and 'FR_CLR' is connected with
July 25, 2012
10:31:12 Deleting the fault record
10:56:12 Changing system setting
On
Event #3
Active group
Active group
'3'
Changed to '4'
Event #2
- 741 -
6F2T0207 (0.01)
July 26, 2012
12:34:51 Deleting the fault record
Pulse train
List of 'Event record1'
Event #3
2012-07-25 10:31:12
F.Record clear 'On'
Event #2
2012-07-25 10:56:12
Set group change
Event #1
On
2012-07-26 12:34:51
Event #1
F.Record clear 'On'
GRE200 (5,6)