Toshiba GR-200-5 Instruction Manual page 779

Multi functional protection ied

Advertisement

Setting
8.3.7
DISTURB_REC(Function ID: 200401)
Setting items
Record Time
Pre-fault Time
Trip Trig.SW
DISTURB_REC(Function ID: 200401)
Setting items
Binary Signal1
Binary Sig.Name1
Binary Signal2
Binary Sig.Name2
Binary Signal3
Binary Sig.Name3
......
......
Binary Signal256
Binary Sig.Name256
DRT_MV(Function ID: 4B0081)
Setting items
OC-DRT-EN
OC-DRT
EF-DRT-EN
EF-DRT
UV-DRT-EN
UV-DRT
UVS-DRT-EN
UVS-DRT
Range
Unit
0.1 - 10.0
s Time for disturbance recording
0.1 - 10.0
s Pre-fault time
Off / On
– Operation with the TRC trip command
Range
Unit
(Preferred DataID)
– Logic signal1 for the operation
(Preferred name)
– Name of the logic signal1
(Preferred DataID)
– Logic signal2 for the operation
(Preferred name)
– Name of the logic signal2
(Preferred DataID)
– Logic signal3 for the operation
(Preferred name)
– Name of the logic signal3
......
– ......
......
– ......
(Preferred DataID)
– Mode setting for the detection
(Preferred name)
– Name of the trigger signal768
Range
Unit
Off / On
– Disturbance Record Trigger OC-DRT enable
0.10 - 150.00
A OC-DRT relay operating value
Off / On
– Disturbance Record Trigger EF-DRT enable
0.10 - 150.00
A EF-DRT relay operating value
Off / On
– Disturbance Record Trigger UV-DRT enable
5.0 - 130.0
– UV-DRT relay operating value
Off / On
– Disturbance Record Trigger UVS-DRT enable
5.0 - 130.0
V UVS-DRT relay operating value
- 759 -
Contents
Contents
Contents
6F2T0207 (0.01)
Default
Note
3.0
0.3
On
Default
Note
See Setting table
in this section
Default
Note
Off
1.00
Off
0.20
Off
0.20
Off
51.0
GRE200 (5,6)