Toshiba GR-200-5 Instruction Manual page 468

Multi functional protection ied

Advertisement

Input
Command "Local-Closing-Control"
511001_7002016D08
DEV01_CONTROL_REQ
ILK condition ("Closing") passed
DPSY01-Close
ILK bypassing
ICB_STATE
From SYNCHK
SYNC01-SYN_CLC
(560001 850B011F59)
SYNC‡‡ bypassing
SCB_STATE
User configurable condition
(PLC#1 connection point)
511001 810201EE57
DPSY01IN_TMP_35
User configurable condition
(PLC#2 connection point)
511001 820201EE5E
DPSY01IN_TMP_44
Figure 4.1-24 Operate closing on the front panel in DPSY01
†Note: The ILK function can provide the operation criteria for "Closing".
‡Note: An "operate condition" signal is generated in the operate-condition logic (see
Figure 4.1-31) when Fixlogic is set for scheme switch [DPSY01-LGCTRCON]. If an
alternative "operate-condition" is required, it can be programmed by the user and
used to replace the signal generated by the original operated-condition logic. The
alternative "operate-condition" can be connected to the above logic using
connection point #1 "User-configurable condition". That is, set the scheme switch
[DPSY01-LGCTRCON] to PLC and use "DPSY01IN_TMP_35".
§§Note: The signal "DPSY01_OEX_BO" is issued when Fixlogic is set for scheme switch
[DPSY01-LGCFEXOT]. The "Operate completed" signal can also be issued from
logic programmed by the user in place of the logic shown in Figure 4.1-20., The
user-programmed logic is connected internally to the signal "Operate completed",
hence this signal is now generated by the user-programmed logic at connection
point #2 "User-configurable condition". That is, set the scheme switch [DPSY01-
LGCFEXOT] to PLC and use "DPSY01IN_TMP_44".
*Note: The user can set the type of output signal. When Var is set for scheme switch
Operate logic in DPSY01
DPSY01 function (Function ID: 511001)
"
DPSY01_OEC_OK_CSF"
(511001 8002011E7F)
Operate Command with ILK
&
condition & synchro-checking
1≥
1≥
[DPSY01-LGCTRCON]
Fixedlogic
Operate condition‡
[DPSY01-LGCFEXOT]
Fixedlogic
[DPSY01-PLSM]*
Var
Fix
Detection of state-change in
a device
S
"
"
DPSY01_EX_CMP
R
(511001 8002011E93)
"DPSY01_OEC_OK_CSF"
(511001 8002011E7F)
- 448 -
"
DPSY01_OEC_OK_CS"
(511001 8102011E82)
1≥
1≥
&
&
&
&
&
1≥
&
&
6F2T0207 (0.01)
Output
[DPSY01-CPW]
1≥
0.1 – 50.0 s
S
R
To BO connection
"DPSY01_OEX_BO"
(511001 8202011DD3)
&
Assign to BOs
To "Wait for a command"
"
DPSY01_EX_CMP
(511001 8002011E93)
Operation Completed
"
DPSY01_EX_FFL
[DPSY01-RST]
(511001 8602011E91)
0
t
1.0s- 100.0s
Operation Failed
GRE200 (5,6)
††
"
"
PLC