OC_MV (Function ID: 440081)
Setting items
OC1-VTFBlk
OC1-OPMD
OC1-UseFor
OC1-ARCBlk
OC1-Act-Stop
OC1-Act-Start
OC1-Act-Run
OC2
OC2-Dir
OC2-Angle
OC2-Timer
DT
OC2
OC2-DPR
TOC2
IEC
OC2
OC2-DPR
OC2-TMS-IEC
TOC2R
UK
OC2
OC2-DPR
OC2-TMS-UK
TOC2R
IEEE
OC2
OC2-DPR
OC2-TMS-
IEEE
OC2-Rtimer
TOC2R
OC2-RTMS-
IEEE
US
OC2
OC2-DPR
OC2-TMS-US
OC2-Rtimer
TOC2R
OC2-RTMS-US
ORG
OC2
OC2-DPR
OC2-TMS-ORG
OC2-Rtimer
TOC2R
OC2-RTMS-
ORG
OC2-k
OC2-a
OC2-c
Range
Unit
Non / Block
- OC1 operation block by VTF
3POR / 2OUTOF3
- OC1 operation mode
Trip / Alarm
- OC1 used for trip or alarm
Non / Block
- Autoreclose block by OC1
Enabling OC1 calculation the motor when
Off / On
-
motor status is in stop status
Enabling OC1 calculation the motor when
Off / On
-
motor status is in start-up status
Enabling OC1 calculation the motor when
Off / On
-
motor status is in running status
NonDir / Forward /
- OC2 directional characteristic
Reverse
-90 – 90
deg OC2 directional characteristic angle
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
IEEE-MI / IEEE-VI /
- OC2 delay type
IEEE-EI / US-CO2 /
US-CO8 / Original
0.02 - 150.00
A OC2 threshold (in DT mode)
10 - 100
% OC2 drop-out/pick-up ratio
0.00 - 300.00
s OC2 operating delay time (in DT mode)
0.02 - 25.00
A OC2 threshold (in IDMT mode)
10 - 100
% OC2 drop-out/pick-up ratio
0.010 - 50.000
- OC2 time multiplier of IEC inverse curve
0.00 - 300.00
s OC2 definite time reset delay
0.02 - 25.00
A OC2 threshold (in IDMT mode)
10 - 100
% OC2 drop-out/pick-up ratio
0.010 - 50.000
- OC2 time multiplier of UK inverse curve
0.00 - 300.00
s OC2 definite time reset delay
0.02 - 25.00
A OC2 threshold (in IDMT mode)
10 - 100
% OC2 drop-out/pick-up ratio
0.010 - 50.000
- OC2 time multiplier of IEEE inverse curve
DEF / DEP
- OC2 reset delay type of IEEE
0.00 - 300.00
s OC2 definite time reset delay
OC2 dependent reset time multiplier of IEEE
0.010 - 50.000
-
inverse curve
0.02 - 25.00
A OC2 threshold (in IDMT mode)
10 - 100
% OC2 drop-out/pick-up ratio
0.010 - 50.000
- OC2 time multiplier of US inverse curve
DEF / DEP
- OC2 reset delay type of US
0.00 - 300.00
s OC2 definite time reset delay
OC2 dependent reset time multiplier of US
0.010 - 50.000
-
inverse curve
0.02 - 25.00
A OC2 threshold (in IDMT mode)
10 - 100
% OC2 drop-out/pick-up ratio
0.010 - 50.000
- OC2 time multiplier of ORG inverse curve
DEF / DEP
- OC2 reset delay type of US
0.00 - 300.00
s OC2 definite time reset delay
OC2 dependent reset time multiplier of ORG
0.010 - 50.000
-
inverse curve
0.00000 - 500.00000
- OC2 user original curve coefficient
0.00000 - 10.00000
- OC2 user original curve coefficient
0.00000 - 10.00000
- OC2 user original curve coefficient
- 33 -
Contents
6F2T0207 (0.01)
Default
Note
Non
3POR
Trip
Block
Off
Off
Off
NonDir
-45
DT
1.00
100
1.00
1.00
100
1.000
0.00
1.00
100
1.000
0.00
1.00
100
1.000
DEF
0.00
1.000
1.00
100
1.000
DEF
0.00
1.000
1.00
100
1.000
DEF
0.00
1.000
0.00000
0.00000
0.00000
GRE200 (5,6)