EF_MV (Function ID:441081)
Setting items
EF2-ARCBlk
EF3
EF3-Dir
Fwd/
EF3-Angle
Rev
EF3-Vpol
EF3-Timer
DT
EF3
EF3-DPR
TEF3
IEC
EF3
EF3-DPR
EF3-TMS-IEC
TEF3R
UK
EF3
EF3-DPR
EF3-TMS-UK
TEF3R
IEEE
EF3
EF3-DPR
EF3-TMS-
IEEE
EF3-Rtimer
TEF3R
EF3-RTMS-
IEEE
US
EF3
EF3-DPR
EF3-TMS-US
EF4-Rtimer
TEF3R
EF3-RTMS-US
ORG
EF3
EF3-DPR
EF3-TMS-ORG
EF3-Rtimer
TEF3R
EF3-RTMS-
ORG
EF3-k
EF3-a
EF3-c
EF3-kr
EF3-b
Output
EF3-VTFBlk
EF3-CTFBlk
EF3-UseFor
EF3-ARCBlk
Range
Unit
Non / Block
- Autoreclose block by EF2
NonDir / Forward /
- EF3 directional characteristic
Reverse
-90 - 90
deg EF3 directional characteristic angle
0.5 - 100.0
V EF3 polarizing voltage level
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
IEEE-MI / IEEE-VI /
- EF3 delay type
IEEE-EI / US-CO2 /
US-CO8 / Original
0.02 - 150.00
A EF3 threshold (in DT mode)
10 - 100
% EF3 drop-out/pick-up ratio
0.00 - 300.00
s EF3 operating delay time (in DT mode)
0.02 - 25.00
A EF3 threshold (in IDMT mode)
10 - 100
% EF3 drop-out/pick-up ratio
0.010 - 50.000
- EF3 time multiplier of IEC inverse curve
0.00 - 300.00
s EF3 definite time reset delay
0.02 - 25.00
A EF3 threshold (in IDMT mode)
10 - 100
% EF3 drop-out/pick-up ratio
0.010 - 50.000
- EF3 time multiplier of UK inverse curve
0.00 - 300.00
s EF3 definite time reset delay
0.02 - 25.00
A EF3 threshold (in IDMT mode)
10 - 100
% EF3 drop-out/pick-up ratio
0.010 - 50.000
- EF3 time multiplier of IEEE inverse curve
DEF / DEP
- EF3 reset delay type of IEEE
0.00 - 300.00
s EF3 definite time reset delay
EF3 dependent reset time multiplier of IEEE
0.010 - 50.000
-
inverse curve
0.02 - 25.00
A EF3 threshold (in IDMT mode)
10 - 100
% EF3 drop-out/pick-up ratio
0.010 - 50.000
- EF3 time multiplier of US inverse curve
DEF / DEP
- EF3 reset delay type of US
0.00 - 300.00
s EF3 definite time reset delay
EF3 dependent reset time multiplier of US
0.010 - 50.000
-
inverse curve
0.02 - 25.00
A EF3 threshold (in IDMT mode)
10 - 100
% EF3 drop-out/pick-up ratio
0.010 - 50.000
- EF3 time multiplier of Original inverse curve
DEF / DEP
- EF3 reset delay type of ORG
0.00 - 300.00
s EF3 definite time reset delay
EF3 dependent reset time multiplier of
0.010 - 50.000
-
Original inverse curve
0.00000 - 500.00000
- EF3 user original curve coefficient
0.00000 - 10.00000
- EF3 user original curve coefficient
0.00000 - 10.00000
- EF3 user original curve coefficient
0.00000 - 500.00000
- EF3 user original curve coefficient
0.00000 - 10.00000
- EF3 user original curve coefficient
Non / Block
- EF3 operation block by VTF
Non / Block
- EF3 operation block by CTF
Trip / Alarm
- EF3 used for trip or alarm
Non / Block
- Autoreclose block by EF3
- 53 -
Contents
6F2T0207 (0.01)
Default
Note
Block
NonDir
-45
3.0
DT
0.30
100
1.00
0.30
100
1.000
0.00
0.30
100
1.000
0.00
0.30
100
1.000
DEF
0.00
1.000
0.30.
100
1.000
DEF
0.00
1.000
0.30
100
1.000
DEF
0.00
1.000
0.00000
0.00000
0.00000
0.00000
0.00000
Non
Non
Trip
Block
GRE200 (5,6)