concerning the operation. Generally, the default error level has been set at level 3 (Minor error)
and level 4 (Alarm) for the faulty state and the undefined state, respectively. However, the user
can program them using settings. For example, when the user wish to program the fault and
undefined states in the DPSY01 function, use the settings [CHK_DPOSSYN1:FLvl] and
[CHK_DPOSSYN1:ULvl], respectively; then, set On for the setting [CHK_DPOSSYN1:Sw].
Error message
(iii)
When the function operates and detects error, an error message can be shown at the LED and
the LCD screen.
Table 10.2-69 Error messages provided by the supervisor in CHK_DPOSSYN/_DPOS
Message and level
XXXX* undefine
Error level
Table 10.2-70 Detailed information in Hexadecimal in CHK_DPOSSYN/_DPOS
Display
area
Top
00000001: Detecting 'undefined'
00000002: Detecting 'faulty'
row
Middle
row
Bottom
row
'Undefine" detected at * of the XXXX function
Minor error (Level 3) for 'Faulty'; Alarm (Level 4) for
Meaning of the detailed information
Left column
(No information is displayed)
(No information is displayed)
Meaning of the information
'Undefine'
- 838 -
6F2T0207 (0.01)
Right column
(No information is displayed)
(No information is displayed)
(No information is displayed)
GRE200 (5,6)