Multi functional protection ied

Advertisement

4.1.6(i)-3)
Note: A supervision of the Binary IO module can detect connection errors for BI circuits
7
Note: The Common control (CMNCTRL) function can test and check the 'Opening' and
8
'Closing' operations performed by the logic. When the user sets Off for scheme
switch [SCDEN], the operation of the logic is blocked if the logic is running in the
same operation-direction compared with the previous operation-direction (i.e.,
when closing (opening) is performed sequentially). On the other hand, if On is set
for the scheme switch, the logic is not blocked.
Note: The user will need to program the PLC logic "Control hierarchy condition". The
9
user is also required to connect the logic condition with the select condition logic
using the connection point "DPSY01IN_TMP_28". For more information, see
Chapter
Table 4.1-7.
Note:
10
Signal name and number
(viii)
Note: The user should note the following descriptions shown in the column "M/O" for
each table:
Table 4.1-2 PLC connection points (Input points for Command 'Closing')
Signal Number
Signal Name
5A0101 800527EF40
DEV01_CL_SYNC_INTER
5A0101 800551EF40
DEV02_CL_SYNC_INTER
5A0101 800526EF40
DEV01_CL_SYNC
5A0101 800550EF40
DEV02_CL_SYNC
5A0101 800525EF40
DEV01_CL_INTERLOCK
5A0101 800549EF40
DEV02_CL_INTERLOCK
5A0101 800524EF40
DEV01_CL_COMMAND
5A0101 800548EF40
DEV02_CL_COMMAND
Table 4.1-3 PLC connection points (Input points for Command 'Open')
Signal Number
Signal Name
5A0101 800523EF40
DEV01_OP_INTERLOCK
5A0101 800547EF40
DEV02_OP_INTERLOCK
5A0101 800522EF40
DEV01_OP_COMMAND
5A0101 800546EF40
DEV02_OP_COMMAND
Control and monitoring application: Control hierarchy
To identify the input points of the DPSY02, see Table 4.1-7.
"O" indicates that the signal is provided for optional use.
"M" indicates that the user should map/set/configure the signal; otherwise, the
user may experience an operational failure if the default settings are
used.
"N/A" indicates that the user cannot change the state of the signal.
Description
DPSY01 PLC Close-control checking with interlock & Sync (PLC#1)
DPSY02 PLC Close-control checking with interlock & Sync (PLC#1)
DPSY01 PLC Close-control with Sync (PLC#2)
DPSY02 PLC Close-control with Sync (PLC#2)
DPSY01 PLC Close-control checking with interlock(PLC#3)
DPSY02 PLC Close-control checking with interlock(PLC#3)
DPSY01 PLC Close-control none checking (PLC#4)
DPSY02 PLC Close-control none checking (PLC#4)
Description
DPSY01 PLC Open-control checking with interlock(PLC#1)
DPSY02 PLC Open-control checking with interlock(PLC#1)
DPSY01 PLC Open-control without checking(PLC#2)
DPSY02 PLC Open-control without checking(PLC#2)
- 436 -
6F2T0207 (0.01)
.
. See PLC#3 of
M/O
O
O
O
O
O
O
O
O
M/O
O
O
O
O
GRE200 (5,6)