Toshiba GR-200-5 Instruction Manual page 146

Multi functional protection ied

Advertisement

Setting
2.9.4
THM_MV (Function ID: 451081)
Setting items
THM-EN
THM
TTHM
TTHM-rad
Type
THM-Itype
THM-q
SW
THMT-EN
THM-UseFor
ALM
THMA-EN
THM-Alarm
Test tool(Function ID: 451081)
Items
Function test
THM-Test
THM-IP
Signal
2.9.5
Signal monitoring point
THM_MV (Function ID: 451081)
Element ID
8000011C23
8000011B60
8400011B23
8300021B23
8100021C23
8100021B60
8000011BB0
8100021BB0
Connection point on PLC logic
THM_MV (Function ID: 451081)
Element ID
800001EBB0
810002EBB0
Range
Unit
Off / On
- Thermal protection scheme switch
0.40 - 10.00
A Thermal overload current
0.5 - 500.0
Thermal time constant
min
0.5 - 500.0
Thermal time constant
min
Max phase/
- Selection of THM equations
Equivalent
0 - 10
- Factor when Equivalent selected
Off / On
- Thermal protection
Trip / Alarm
- THM used for trip or alarm
Off / On
- Thermal alarm switch
50 - 100
% Thermal alarm level multiplier
Range
Unit
Off / On
- Thermal protection scheme switch
0.00 - 5.00
A Thermal overload current
Name
THM-A
THM-ALARM
THM-OPT-ALARM
THM-OPT-TRIP
THM-T
THM-TRIP
THMA_BLOCK
THMT_BLOCK
Name
Description
THMA_BLOCK
THM protection for Alarm block command
THMT_BLOCK
THM protection for Trip block command
- 126 -
Contents
Contents
Description
THM relay element operated (Alarm)
THM protection Alarm signal
THM protection operated (Alarm)
THM protection operated (Trip)
THM relay element operated (Trip)
THM protection Trip signal
THM protection for Alarm block command
THM protection for Trip block command
6F2T0207 (0.01)
Default
Note
Off
1.00
10.0
10.0
Equivalent
0
Off
Trip
Off
80
Default
Note
Off
0.00
GRE200 (5,6)