Mapping output data
(ii)
The user should group the DPOS01 signals with regard to GOOSE and REPORT; the user
should map them for IEC 61850 communication using GR-TIEMS. (Figure 4.2-55 illustrates
how to map a signal); it indicates that the signals for the DPOS01 function are required to map
for IEC 61850 communications.
Table 4.2-34 Mapping signals required for CSWI4 object in DPOS01 function
Object_reference
Ctrl/CSWI4$Pos$origin
orCat
Ctrl/CSWI4$Pos$origin
orIdent
Ctrl/CSWI4$Pos
stVal
Ctrl/CSWI4$Pos
q
Ctrl/CSWI4$Pos
t
Ctrl/CSWI4$Pos
stSeld
Note: "Status (ST)" is defined in the function constraint (FC) of the IEC 61850 standard.
Figure 4.2-55 Attribute mapped into DPCSO object of CSWI4
Mapping input data
(iii)
The DPOS01 function can receive three commands "select, operate, and cancel". Thus, the user
should map the input-point "
4.2-35
shows the input "DEV01_CONTROL_REQ" and the Object reference
the user should map the input-point to the Object reference having
map a signal.
shows how to
†Note: The attribute is defined in the IEC 61850 standard; "CO" stands for "Control" in
the functional constraint (FC).
Attribute
Type
orCategory
Octet64
Dbpos
Quality
Timestamp
BOOLEAN
DEV01_CONTROL_REQ" to the IEC61850 communication.
- 546 -
FC
Signal Number
ST
512001 3103011008
ST
512001 6A03011009
ST
512001 3103011001
ST
512001 3103011005
ST
512001 9003011006
ST
512001 0003011D90
Drag and drop
6F2T0207 (0.01)
Signal Name
DPOS01_3PH_ORCAT
DPOS01_3PH_ORIDENT
DPOS01_3PH_STATE
DPOS01_3PH_QUALITY
DPOS01_3PH_TIMESTAMP
DPOS01_STD_RPT
"Ctrl/CSWI4$Pos"
attribute CO†. Figure 4.2-56
GRE200 (5,6)
Table
;

Advertisement

loading

This manual is also suitable for:

Gr-200 seriesGr-200-6