Toshiba GR-200-5 Instruction Manual page 445

Multi functional protection ied

Advertisement

Input
Command "Remote-Closing Control"
511001 7002016D08
DEV01_CONTROL_REQ
ILK† condition ("Closeing") passed
DPSY01-Close
From SYNCHK
SYNC01-SLD_VCS‡‡
(560001 840B011F58)
Either "SBO mode" or "DIR mode"
(e.g., "ctlmodel" in IEC61850*)
Figure 4.1-2 Select logic 'Closing' from the remote-end in DPSY01
†Note: The Software interlocking (ILK) function can provide the operation criteria for
"Closing". The ILK function is discussed separately; note that the operation
criteria is defined by the ILK function itself (i.e., the user cannot set the
condition).
‡Note: A "select condition" signal is provided from the select condition scheme. For more
information, see Figure 4.1-13.
*Note: The DPSY01 function can run in either the "SBO mode" or the "DIR mode". The
user can use a signal called "ctlmodel" when communication is implemented using
IEC61850. To use this signal, the user must map it for IEC61850 communication.
Note: To identify the input and output points of the DPSY02 logic, see Table 4.1-5 and
††
Table 4.1-9.
Note: The synchronism voltage check is executed by the SYNCHK function.
‡‡
Note: A timer is provided to determine an operation failure. The maximum value of the
§§
settings [SYNC01_TLRDIDRLI] or [SYNC01_TDRDI] is used as the decision time.
For more information on settings, see the SYNDIF function.
Selection logic in DPSY01
DPSY01 function (Function ID: 511001)
For SBO operation
Select command with ILK†
condition & synchro-check‡‡
For DIR operation
Operate command with ILK†
condition & synchro-check‡‡
Voltage condition
For SBO operation
Select command with
synchro-check‡‡
For DIR operation
Operate command with
synchro-check‡‡
For SBO operation
Select command with ILK†
condition
For DIR operation
Operate command with ILK†
condition
For SBO operation
Select command without condition
For DIR operation
Operate command without
condition
In SBO operate
In DIR operate
Select condition‡
- 425 -
1≥
&
&
&
0
t
0.1s
&
Timer§§
0
t
0
&
0.0 to 5.0 s
0.6s
&
&
&
&
6F2T0207 (0.01)
Output
To "Wait for a next
command"
To BO connection
DPSY01_OSL_BO_FLG"
(511001 8602011DC6)
Select "Closing"
To "Wait for a command"
t
Select "Failed"
††
GRE200 (5,6)