OC_MV (Function ID: 440081)
Setting items
OC3-RTMS-
ORG
OC3-k
OC3-a
OC3-c
OC3-kr
OC3-b
Output
OC3-2fBlk
OC3-VTFBlk
OC3-OPMD
OC3-UseFor
OC3-ARCBlk
OC3-Act-Stop
OC3-Act-Start
OC3-Act-Run
OC4
OC4-Dir
OC4-Angle
OC4-Timer
DT
OC4
OC4-DPR
TOC4
IEC
OC4
OC4-DPR
OC4-TMS-IEC
TOC4R
UK
OC4
OC4-DPR
OC4-TMS-UK
TOC4R
IEEE
OC4
OC4-DPR
OC4-TMS-
IEEE
OC4-Rtimer
TOC4R
OC4-RTMS-
IEEE
US
OC4
OC4-DPR
OC4-TMS-US
OC4-Rtimer
TOC4R
OC4-RTMS-US
ORG
OC4
Range
Unit
OC3 dependent reset time multiplier of ORG
0.010 - 50.000
-
inverse curve
0.00000 - 500.00000
- OC3 user original curve coefficient
0.00000 - 10.00000
- OC3 user original curve coefficient
0.00000 - 10.00000
- OC3 user original curve coefficient
0.00000 - 500.00000
- OC3 user original curve coefficient
0.00000 - 10.00000
- OC3 user original curve coefficient
Non / Block-AllP /
- OC3 operation block by 2f-detection
Block-PerP
Non / Block
- OC3 operation block by VTF
3POR / 2OUTOF3
- OC3 operation mode
Trip / Alarm
- OC3 used for trip or alarm
Non / Block
- Autoreclose block by OC3
Enabling OC3 calculation the motor when
Off / On
-
motor status is in stop status
Enabling OC3 calculation the motor when
Off / On
-
motor status is in start-up status
Enabling OC3 calculation the motor when
Off / On
-
motor status is in running status
NonDir / Forward /
- OC4 directional characteristic
Reverse
-90 – 90
deg OC4 directional characteristic angle
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
IEEE-MI / IEEE-VI /
- OC4 delay type
IEEE-EI / US-CO2 /
US-CO8 / Original
0.02 - 150.00
A OC4 threshold (in DT mode)
10 - 100
% OC4 drop-out/pick-up ratio
0.00 - 300.00
s OC4 operating delay time (in DT mode)
0.02 - 25.00
A OC4 threshold (in IDMT mode)
10 - 100
% OC4 drop-out/pick-up ratio
0.010 - 50.000
- OC4 time multiplier of IEC inverse curve
0.00 - 300.00
s OC4 definite time reset delay
0.02 - 25.00
A OC4 threshold (in IDMT mode)
10 - 100
% OC4 drop-out/pick-up ratio
0.010 - 50.000
- OC4 time multiplier of UK inverse curve
0.00 - 300.00
s OC4 definite time reset delay
0.02 - 25.00
A OC4 threshold (in IDMT mode)
10 - 100
% OC4 drop-out/pick-up ratio
0.010 - 50.000
- OC4 time multiplier of IEEE inverse curve
DEF / DEP
- OC4 reset delay type of IEEE
0.00 - 300.00
s OC4 definite time reset delay
OC4 dependent reset time multiplier of IEEE
0.010 - 50.000
-
inverse curve
0.02 - 25.00
A OC4 threshold (in IDMT mode)
10 - 100
% OC4 drop-out/pick-up ratio
0.010 - 50.000
- OC4 time multiplier of US inverse curve
DEF / DEP
- OC4 reset delay type of US
0.00 - 300.00
s OC4 definite time reset delay
OC4 dependent reset time multiplier of US
0.010 - 50.000
-
inverse curve
0.02 - 25.00
A OC4 threshold (in IDMT mode)
- 35 -
Contents
6F2T0207 (0.01)
Default
Note
1.000
0.00000
0.00000
0.00000
0.00000
0.00000
Non
Non
3POR
Trip
Block
Off
Off
Off
NonDir
-45
DT
1.00
100
1.00
1.00
100
1.000
0.00
1.00
100
1.000
0.00
1.00
100
1.000
DEF
0.00
1.000
1.00
100
1.000
DEF
0.00
1.000
1.00
GRE200 (5,6)