Toshiba GR-200-5 Instruction Manual page 153

Multi functional protection ied

Advertisement

Setting
2.11.2
CLP_MV (Function ID: 481081) at Common tree
Setting items
CLP-EN
CLP
CLP-SG
TCLP-EN
TCLP-RESET
CLP-DOEN
DOEN
OCCLP
TCLP-DO
Test tool(Function ID: 481081)
Item
Function test
CLP-Test
Signal
2.11.3
PLC monitoring point
CLP_MV (Function ID: 481081)
Element ID
8000001C20
8100001C21
8200001C22
8000001B60
8100001B61
8200001B62
8300001B63
3100001B64
Range
Unit
Off / On
- Cold load protection scheme switch
Group1 / Group2 /
Group3 / Group4 /
- Applied setting group at cold load mode
Group5 / Group6 /
Group7 / Group8
0 - 10000
s Cold load enable time
0 - 10000
s Cold load reset time
Off / On
- Cold load drop-out enable
0.02 - 15.00
A Cold load drop-out current threshold
0.00 - 100.00
s Cold load drop-out time
Range
Unit
Off / STATE0 /
- Forcibly changing to CLP state
STATE3
Name
Description
OCCLP-A
OCCLP relay element operated (phase-A)
OCCLP-B
OCCLP relay element operated (phase-B)
OCCLP-C
OCCLP relay element operated (phase-C)
CLP STATE0
The scheme is in STATE0
CLP STATE1
The scheme is in STATE1
CLP STATE2
The scheme is in STATE2
CLP STATE3
The scheme is in STATE3
CLP STATE2OR3
The scheme is in STATE2OR3
- 133 -
Contents
Contents
6F2T0207 (0.01)
Default
Note
Off
Group1
100
100
Off
0.50
0.00
Default
Note
Off
GRE200 (5,6)