6F2T0207 (0.01)
Thermal Curves of
Locked Rotor Protection (I
2.5x[Mot-Ir])
Current (A)
Figure 2.28-13 Thermal curve of locked rotor protection (I ≥ 2.5x[Mot-Ir])
- Motor rated current : [Mot-Ir] = 1.00A
- Motor start-up current (Ist) : [Mot-LKRT-IS] = 5.00A (5 times motor rated current)
- Allowable locking time in the cold state (Tsc) : [T-Mot-LKRT] = 10s
- Allowable thermal capacity of rotor (θrm) : [Mot-LKRT] = 150%
GRE200 (5,6)
- 335 -