Download Print this page

Toshiba GR-200-5 Instruction Manual page 393

Multi functional protection ied

Advertisement

Mapping for IEC61850 communication
3.4.5
The user can operate the LEDR function over IEC 61850 communication following mapping
using GR-TIEMS. Note that the LEDR function is designed for "LEDRs" in the IEC 61850
standard for communication. The user should follow these steps, each of which is discussed
below:
Step1:
Editing Logical Node
Step2:
Mapping output data
Step3:
Mapping input data
Editing Logical Node
(i)
The user will need to create a logical node (LN) for the LEDR function. Figure 3.4-10
exemplifies the editing of a LN; the LN "logical node zero (LLN0)" is chosen for the LERD
function. Either the SBO mode or the DIR mode should be chosen in the editing for the LN.
Figure 3.4-10 Defining "LEDRs" object in LLN0 logic node
Defining SBO mode
Figure 3.4-11 exemplifies the LEDR logic node saved as "LLN0". In the SBO mode, the user
should select the following items in the "LLN0$LEDRs" using GR-TIEMS:
SBO defined in LN
- 373 -
6F2T0207 (0.01)
GRE200 (5,6)

Advertisement

loading

This manual is also suitable for:

Gr-200 seriesGr-200-6