Table 5.6-6 Setting items for binary input circuits of IO#2 and IO#3
Setting of BIO_SLOT_MV (Function ID: 200B42/200B43)
Setting items
Common
CMP_NUM
BITH
BI1
BI1_CPL
On Delay Timer
Off Delay Timer
INVERSE-SW
BI2
BI2_CPL
On Delay Timer
Off Delay Timer
INVERSE-SW
BI3
BI3_CPL
On Delay Timer
Off Delay Timer
INVERSE-SW
...
....
BI7
BI7_CPL
On Delay Timer
Off Delay Timer
INVERSE-SW
BI8
BI8_CPL
On Delay Timer
Off Delay Timer
INVERSE-SW
Range
Unit
4 - 9
- Counting number to ignore input signals
Level_1 / Level_2 /
- Threshold level at BI1–BI8 of MV-BIO1
Level_3
Off / On
- Switch for programming logic on binary input1
0.000 - 300.000
s Setting value for On-delay timer
0.000 - 300.000
s Setting value for Off-delay timer
Normal / Inverse
- Switch to inverse a binary input
Off / On
- Switch for programming logic on binary input2
0.000 - 300.000
s Setting value for On-delay timer
0.000 - 300.000
s Setting value for Off-delay timer
Normal / Inverse
- Switch to inverse a binary input
Off / On
- Switch for programming logic on binary input3
0.000 - 300.000
s Setting value for On-delay timer
0.000 - 300.000
s Setting value for Off-delay timer
Normal / Inverse
- Switch to inverse a binary input
....
Off / On
- Switch for programming logic on binary input7
0.000 - 300.000
s Setting value for On-delay timer
0.000 - 300.000
s Setting value for Off-delay timer
Normal / Inverse
- Switch to inverse a binary input
Off / On
- Switch for programming logic on binary input8
0.000 - 300.000
s Setting value for On-delay timer
0.000 - 300.000
s Setting value for Off-delay timer
Normal / Inverse
- Switch to inverse a binary input
- 662 -
Contents
....
6F2T0207 (0.01)
Default
Note
4
Level_1
Off
0.000
0.000
Normal
Off
0.000
0.000
Normal
Off
0.000
0.000
Normal
....
Off
0.000
0.000
Normal
Off
0.000
0.000
Normal
GRE200 (5,6)