Download Print this page

Toshiba GR-200-5 Instruction Manual page 465

Multi functional protection ied

Advertisement

[DPSY01-PLSM], the output period of the signal is defined by the setting
[DPSY01-CPW]. When Fix is set, the signal ceases when the 43-switch is changed.
Note: To identify the input and output signal-points of the DPSY02 logic, see Table
††
4.1-14 for PLC#1, Table 4.1-15 for PLC#2, Table 4.1-19, and Table 4.1-20 for
output signals.
Note: The "Operate failed" signal is issued when the state-change is not detected when
‡‡
the time set by the [DPSY01-RST] has been reached.
Output signal to BO
The DPSY01 function, in Figure 4.1-20, can issue an "Operate" signal at the output point
"DPSY01_OEX_BO", when the DPSY01 function determines that the received signal "Remote-
Closing-Control" is true.
Receiving "operate command Open" from the remote-end
(ii)
Figure 4.1-21 depicts the reception of the operate command 'Open' from the remote-end.
Wait for a command
Select stage
Select command Closing from the remote-end
Select command Open from the remote-end
Select command Closing from the local-end
Select command Open from the local-end
Select command Closing by the PLC function
Select command Open by the PLC function
Figure 4.1-21 Outline of operate command 'Open'
Mapping required for Input point from communication
Figure 4.1-22 illustrates the operate logic when an "Operate command (Remote-Open-Control)"
signal is applied to the DPSY01 logic. The input-point "DEV01_CONTROL_REQ" is used for
the reception of the "Operate command Open (Remote-Open-Control)".
Wait for a next command
Operate command Closing from the remote-end
Operate command Open from the remote-end
Operate logic
Signal reception in
IEC61850
Operate command Closing l from the local-end
Operate command Open from the local-end
Operate command Closing by the PLC function
Operate command Open by the PLC function
- 445 -
6F2T0207 (0.01)
Success
Operation
Signal output
decision
Do nothing
Failed
GRE200 (5,6)

Advertisement

loading

This manual is also suitable for:

Gr-200 seriesGr-200-6