SEF_MV (Function ID: 442081)
Setting items
SEF3-TMS-
ORG
SEF3-Rtimer
Rtimer
TSEF3R
SEF3-RTMS-
ORG
SEF3-k
SEF3-a
SEF3-c
SEF3-kr
SEF3-b
OUTPUT
SEF3-2fBlk
SEF3-VTFBlk
SEF3-UseFor
SEF3-ARCBlk
SEF4
SEF4-EN
SEF4 Directio
SEF4-Dir
n
Pol.
SEF4-Angle
SEF4-Vpol
RP
RP4-EN
RP4
SEF4 characteristic
SEF4-Timer
DT
SEF4
SEF4-DPR
TSEF4
IEC
SEF4
SEF4-DPR
SEF4-TMS-
IEC
TSEF4R
UK
SEF4
SEF4-DPR
SEF4-TMS-UK
TSEF4R
IEEE
SEF4
SEF4-DPR
SEF4-TMS-
IEEE
Rtimer
SEF4-Rtimer
TSEF4R
SEF4-RTMS-
IEEE
US
SEF4
SEF4-DPR
SEF4-TMS-US
Rtimer
SEF4-Rtimer
TSEF4R
SEF4-RTMS-
US
Range
Unit
0.010 - 50.000
- SEF3 time multiplier of Original inverse curve
DEF / DEP
- SEF3 reset delay type of ORG
0.00 - 300.00
s SEF3 definite time reset delay
SEF3 dependent reset time multiplier of
0.010 - 50.000
-
Original inverse curve
0.00000 - 500.00000
- SEF3 user original curve coefficient
0.00000 - 10.00000
- SEF3 user original curve coefficient
0.00000 - 10.00000
- SEF3 user original curve coefficient
0.00000 - 500.00000
- SEF3 user original curve coefficient
0.00000 - 10.00000
- SEF3 user original curve coefficient
Non / Block
- SEF3 operation block by 2f-detection
Non / Block
- SEF3 operation block by VTF
Trip / Alarm
- SEF3 used for trip or alarm
Non / Block
- Autoreclose block by SEF3
Off / On
- SEF4 protection enable
NonDir / Forward /
- SEF4 selection of protection direction
Reverse
-90 - 90
deg SEF4 polarizing angle in directional element
3.0
V SEF4 polarizing vol. in directional element
Off / On
- Enabling RP in directional protection
0.00 – 100.00
W Threshold of residual power element
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
IEEE-MI / IEEE-VI /
- SEF4 delay type
IEEE-EI / US-CO2 /
US-CO8 / Original
0.001 - 1.000
A SEF4 threshold (in DT mode)
10 - 100
% SEF4 drop-out/pick-up ratio
0.00 - 300.00
s SEF4 operating delay time (in DT mode)
0.001 - 1.000
A SEF4 threshold (in IDMT mode)
10 - 100
% SEF4 drop-out/pick-up ratio
0.010 - 50.000
- SEF4 time multiplier of IEC inverse curve
0.00 - 300.00
s SEF4 definite time reset delay
0.001 - 1.000
A SEF4 threshold (in IDMT mode)
10 - 100
% SEF4 drop-out/pick-up ratio
0.010 - 50.000
- SEF4 time multiplier of UK inverse curve
0.00 - 300.00
s SEF4 definite time reset delay
0.001 - 1.000
A SEF4 threshold (in IDMT mode)
10 - 100
% SEF4 drop-out/pick-up ratio
0.010 - 50.000
- SEF4 time multiplier of IEEE inverse curve
DEF / DEP
- SEF4 reset delay type of IEEE
0.00 - 300.00
s SEF4 definite time reset delay
SEF4 dependent reset time multiplier of IEEE
0.010 - 50.000
-
inverse curve
0.001 - 1.000
A SEF4 threshold (in IDMT mode)
10 - 100
% SEF4 drop-out/pick-up ratio
0.010 - 50.000
- SEF4 time multiplier of US inverse curve
DEF / DEP
- SEF4 reset delay type of US
0.00 - 300.00
s SEF4 definite time reset delay
SEF4 dependent reset time multiplier of US
0.010 - 50.000
-
inverse curve
- 86 -
Contents
6F2T0207 (0.01)
Default
Note
1.000
DEF
0.00
1.000
0.00000
0.00000
0.00000
0.00000
0.00000
Non
Non
Trip
Block
Off
Non
-45
3.0
Off
0.00
DT
0.010
100
1.00
0.010
100
1.000
0.00
0.010
100
1.000
0.00
0.010
100
1.000
DEF
0.00
1.000
0.010
100
1.000
DEF
0.00
1.000
GRE200 (5,6)