Toshiba GR-200-5 Instruction Manual page 287

Multi functional protection ied

Advertisement

Protection
functions
FC01
FC02
FC40
Trip signal generation scheme
800000EBBE OPT.P-N_ADD
Figure 2.23-5 Scheme logic for Alarm-signal generation
When an additional relay, external to the IED is utilized, an alarm signal can be provided,
indicating for example a Line-to-Line (LL) fault and others. If the user wishes to record the
alarm, then PLC connection points 'OPT.P-A_ADD' and others can be used. If the additional
relay is designed to operate for a ground fault, use the alternative PLC connection point
'OPT.P-N_ADD'
Setting
2.23.4
(No setting items exist)
FC*-OPT-AR
≥1
880000EBB8 OPT.P-A_ADD
FC*-OPT-BR
≥1
890000EBB9 OPT.P-B_ADD
FC*-OPT-CR
≥1
8A0000EBBA OPT.P-C_ADD
FC*-OPT-ABR
≥1
8C0000EBBB OPT.P-AB_ADD
FC*-OPT-BCR
≥1
8D0000EBBC OPT.P-BC_ADD
FC*-OPT-CAR
≥1
8E0000EBBD OPT.P-CA_ADD
FC*_OPT-ALARM
≥1
840000EBB7 OPT-ALARM_ADD
GEN.TRIP
- 267 -
8000001B66
≥1
&
OPT-AR
8100001B67
≥1
OPT-BR
&
8200001B68
≥1
OPT-CR
&
8400001B69
&
OPT-ABR
8500001B6A
OPT-BCR
8600001B6B
OPT-CAR
8400001B64
≥1
GEN.ALARM
6F2T0207 (0.01)
To Recording function
8000001B71
OPT.PHASE-A
8000001B72
OPT.PHASE-B
8000001B73
OPT.PHASE-C
8000001B74
OPT.PHASE-N
8000001B77
GEN.TRIP_ALARM
GRE200 (5,6)