Toshiba GR-200-5 Instruction Manual page 690

Multi functional protection ied

Advertisement

Setting of BIO_SLOT_MV (Function ID: 200B42/200B43)
Setting items
On Delay Timer
0.000 - 300.000
Off Delay Timer
0.000 - 300.000
INVERSE-SW
Normal / Inverse
Off / Delay / Dwell
TIMER-SW
Logic Timer
0.000 - 300.000
Reset signal
(Preferred Data ID)
Range
Contents
Unit
Setting value for On-delay timer
s
s
Setting value for Off-delay timer
Switch to inverse a binary output
-
Selection of Logic circuit
-
/ Latch
Off delay timer value: "Delay" and
s
"Dwell" circuit
Reset signal selection for "Latch" circuit
-
GRE200-5
0.000
0.000
Normal
Off
0.000
Not assigned
- 670 -
6F2T0207 (0.01)
Default
GRE200-6
Note
0.000
0.000
Normal
Off
0.000
Not assigned
GRE200 (5,6)
Note