Setting
4.3.9
PWRQTY (FunctionID:543081)
Setting items
PWRQTY-EN
Commo n
AverageTime-V
AverageTime-I
HHD
LimitTHD
LimitTDD
VAR
Swl-ALRM
Swl-HYST
Dip-ALRM
Dip-HYST
Dip-CONFT
Intrpt-ALRM
Intrpt-HYST
PWRQTY-SDB
PWRQTY-ZDB
PWRQTY-PDB
Range
Unit
Off/On
- Control switch for PWRQTY
THD average time measured with applied
1-600
s
voltage
THD and TDD average times measured with
1-600
s
entering current
0.1-60.0
% Alarm level at THD
0.1-60.0
% Alarm level at TDD
110-140
% Alarm level at SWELL
0-5
% Hysteresis at SWELL ALRM
11-90
% Alarm level at DIP/SAG
0-5
% Hysteresis at DIP/SAG ALRM
0.0-1.5
s Check timer for DIP/SAG ALRM
0-10
% Alarm level at INTERRUPT
0-5
% Hysteresis at INTERRUPT
0.0-10.0
% Sending DeadBand setting
0.0-10.0
% Zero DeadBand setting
Number of Periodic DeadBand setting
0-20
-
multiplied powered by 500[ms]
- 575 -
Contents
6F2T0207 (0.01)
Default
Note
Off
60s
60s
16.00%
16.00%
110%
2
80%
2
0s
0%
2%
0.00%
0.00%
0