Multi functional protection ied

Advertisement

Input
Command "PLC-On-Control" requiring ILK† check
(PLC#3 connection point)
512001 800301EE33
DEV01_CL_INTERLOCK
Command "PLC-On-Control" not requiring ILK† check
(PLC#4 connection point)
512001 800301EE32
DEV01_CL_COMMAND
ILK† condition ("ON") passed
DPOS01-Close
User configurable condition
(PLC#1 connection point)
512001 810301EE57
DPOS01IN_TMP_35
User configurable condition
(PLC#2 connection point)
512001 820301EE5E
DPOS01IN_TMP_42
"DPOS01_OEC_OK_CSF"
Figure 4.2-28 Operate On by the PLC function in DPOS01
†Note: The ILK function can provide the operation criteria for "On".
‡Note: An "operate condition" signal is generated in the operate-condition logic (see
Figure 4.2-31), when Fixlogic is set for scheme switch [DPOS01-LGCTRCON]. If
an alternative "operate-condition" programmed by the user is required in place of
the signal generated by the original operate-condition logic, connect the
alternative "operate-condition" to the logic shown in Figure 4.2-28 using
connection point #1 "User configurable condition". That is set the scheme switch
[DPOS01-LGCTRCON] to PLC and use "DPOS01IN_TMP_35".
§§Note: The "DPOS01_OEX_BO" signal is issued when Fixedlogic is set for scheme
switch [DPOS01-LGCFEXOT]. If the signal is to be issued from the logic
programmed by the user instead of the logic shown in Figure 4.2-20, connect the
"Operate completed" signal generated in the user-programmed logic to connection
point #2 "User configurable condition". That is, set the scheme switch [DPOS01-
LGCFEXOT] to PLC and use "DPOS01IN_TMP_42".
*Note: The user can select a type of output signal. When Var is set for scheme switch
[DPOS01-PLSM], the output period of the signal is defined by the setting applied
to [DPOS01-CPW]. When Fix is set, the signal ceases when the 43-switch is
changed.
Operate logic in DPOS01
DPOS01 function (Function ID: 512001)
Operate Cmd.
with ILK † condition
&
Operate Cmd.
without ILK † condition
[DPOS01-LGCTRCON]
Fixedlogic
Operate condition‡
[DPOS01-LGCFEXOT]
Fixedlogic
[DPOS01-PLSM]*
Var
Fix
Detection of state-change in a device
- 519 -
" DPOS01_OEC_OK_CS"
(512001 8103011E82)
1≥
1≥
&
&
&
&
&
1≥
&
&
6F2T0207 (0.01)
Output
" DPOS01_OEC_OK_CSF"
(512001 8003011E7F)
[DPOS01-CPW]
1≥
0.1 – 50.0 s
S
R
To BO connection
"DPOS01_OEX_BO" §§
(512001 8203011DD3)
&
Assign to BOs
To "Wait for a command"
" DPOS01_EX_CMP "
(512001 8003011E93)
Operate Completed
" DPOS01_EX_FFL "
[DPOS01-RST]
(512001 8603011E91)
0
t
1.0s- 100.0s
Operate Failed
††
GRE200 (5,6)
††