Download Print this page

Toshiba GR-200-5 Instruction Manual page 652

Multi functional protection ied

Advertisement

Connection styles and polarity
5.4.4
In order that the relay can run in versatile environment, flexible operations are permitted on
the circuits of VCT; one of styles should be selected depending on the connection of CT/VT and
polarity. A style is determined by the required connection, which is equal to the actual wiring.
Figure 5.4-5 shows menus on the LCD screens about the styles and CT priorities settings.
AC Analog Input
10:48
AI#1
APPL-VCT
Setting of APPL-VCT (FEP_COMMON_MV: Function ID: 7F0081)
Setting items
Conn-CT
2P_Type
Conn-IeCT
Connection
Conn-IseCT
setting
Conn-VT
Conn-VeVT
Conn-VsVT
Pol-CT
Polarity
Pol-IeCT
setting
Pol-IseCT
Note: Term 'N/A' represents 'Not applicable' herein.
CT connection style
5.4.5
Cable connections can depend on the CT arrangements and their wirings; hence, the
connection styles are provided for actual user environments. Several CT connection styles are
provided (No. 101–122) in order that the CT can get three-phase current, zero-sequence phase
current and residual current.
APPL-VCT
1/2
10:48
>
Conn-CT
>
2P
Conn-IeCT
Residual
Conn-Ise
Use
Conn-VeVT
Use
Conn-VsVT
Use
Polarity Change >
Figure 5.4-5 Instruction of CT connection settings
Table 5.4-1 Style and polarity settings for CT and VT
Range
No use / 3P / 2P
1 / 2
No use / Residual /
Independent
No use / Use
No use / 3PN / 3PP /
2PP / 1PN / 1PP
No use / Use
No use / Use
Negative / Positive
Negative / Positive
Negative / Positive
1/7
+
Setting for
'Connection style'
+
+
+
+
Setting for
'Polarity '
Switch contents
Units
CT connection style
Switch for setting [Conn-CT]=2P
IeCT connection style
IseCT connection style
VT connection style
VeVT connection style
VsVT connection style
Polarity at CT
Polarity at IeCT
Polarity at IseCT
- 632 -
6F2T0207 (0.01)
Conn-CT
10:48
1/1
2P_Type
+
1
Polarity Change
10:48
1/3
Pol_CT
+
Positive
Pol_IeCT
Positive
Pol_IseCT
Positive
Model GRE200-
5
3P
1
Residual
(N/A)
(N/A)
Use
3PN
Use
Use
Positive
Positive
(N/A)
(N/A)
Positive
GRE200 (5,6)
6

Advertisement

loading

This manual is also suitable for:

Gr-200 seriesGr-200-6