Download Print this page

Toshiba GR-200-5 Instruction Manual page 404

Multi functional protection ied

Advertisement

Select condition
(ii)
Figure 3.5-8 shows the select condition logic in the GCNT01 function. When resetting the
counter is performed from the "Statics sub-menu" in the HMI operation†, the user should set
On for scheme switch [GCNT01-HMI].
†Note: The HMI operation is discussed in
(→p. 989).
Other devices traveling detected*3
From Control hierarchy *5
540001 800E00ED5A
GCNT00IN_TMP_51
From CMNCTRL
Serious error detection
SERI_ERR
Figure 3.5-7 Select condition logic for Reset in GCNT01
Note: If the event "device-travelling" is detected, it indicates that another operator is
3
changing the status of a device. Thus, the IED should inhibit the operation of any
device for the duration that the event is detected. The detected signal is denoted
as "Traveling OR" in Table 3.5-2.
Note: Criteria "unmatched conditions" are decided when the "Test-bit status" in a
4
command is not identical to the "IED test status".
Note: The user will need to program the PLC logic "Control hierarchy condition". The
5
user is also required to connect the logic condition with the select condition logic
using the connection pint "GCNT00IN_TMP_51" (see Table 3.5-3). For more
information, see Chapter 3.3.
GCNT01 function (Function ID: 540001)
Traveling OR
Unmatched condition detected *4
[GCNT01-HMI]
On
[DPOS01-EN]
On
- 384 -
Chapter User interface: Monitoring sub-menu
1≥
&
6F2T0207 (0.01)
To select logic
Select condition
&
GRE200 (5,6)