Download Print this page

Toshiba GR-200-5 Instruction Manual page 975

Multi functional protection ied

Advertisement

Note:
TR and TL are set in Common setting.
1
Note:
Settings of the test mode is described later.
2
(2) If one of COT is specified per No., the frame is always supplemented with the
specified COT regardless of cause of transmission.
(3) If COT=9 is specified, the frame become the object of GI and is sent back when the
GI request frame is received. Time-tagged message is sent back in order of No.
instead of order of INF.
Table 11.5-8 shows the summary of (1), (2) and (3) above.
Table 11.5-8 COT setting pattern and COT supplemented frame
COT setting
pattern
1
9
11
Note: When being in the test mode, the COT=1(Spontaneous) is shifted to 7(Test
mode)
COT supplemented frame when status changes
12
Always "1"
Events don't occur.
Always "11"
Always "12"
Always "1"
"11" (cause at local) or "1" (other causes)
"12" (cause at remote) or "1" (other causes)
Always "11"
Always "12"
"11" (cause at local) or "12" (cause at remote) or "1"
(other causes)
"11" (cause at local) or "1" (other causes)
"12" (cause at remote) or "1" (other causes)
"11" (cause at local) or "12" (cause at remote) or "1"
(other causes)
"11" (cause at local) or "12" (cause at remote) or "1"
(other causes)
"11" (cause at local) or "12" (cause at remote) or "1"
(other causes)
Always "1" in spite of cause of event occurrence
- 955 -
6F2T0207 (0.01)
GI
No
Yes
No
No
Yes
No
No
Yes
Yes
No
Yes
Yes
No
Yes
Yes
No
GRE200 (5,6)

Advertisement

loading

This manual is also suitable for:

Gr-200 seriesGr-200-6