Toshiba GR-200-5 Instruction Manual page 944

Multi functional protection ied

Advertisement

Modbus TCP
11.4.5
The Modbus TCP can support the communication over the Ethernet. The Ethernet provides
the Modbus TCP (see Figure 11.4-1). TCP and IP layers detect errors over the Ethernet, so the
error check one is omitted here. The Modbus TCP will be set when the setting
[MODBUS_SELECT] = TCP.
Communication
10:48
1/7
LAN
USBCOM
RS485
SLAVE PROTOCOL
IEC61850
IEC103
MODBUS
Note: Each IED (Slave) can be identified by an IP address. Thus, the user does not have
to set the setting [MODBUS ADDR] (see sec. 11.4.4(ii)-1) when the TCP is set.
Network structure
(i)
Figure 11.4-9 shows the IEDs(Slave) connect with substation computer(s)(Master) through
Ethernet ring LAN. IEDs can communicate with up to 6 substation computers, and serval
architectures and speeds can be defined by the LAN communication modules†.
Remote monitoring
Message frame
TCP slave response
IED (Slaves)
Device1
(192.168.1.11)
Figure 11.4-9 Ethernet ring LAN by Modbus TCP/IP
†Note: See Chapter
can set an IP address with setting [IPADDRESS1] (see Figure 11.2-1).
MODBUS
10:48
>
MODBUS_BLK
>
Off
>
MODBUS ADDR
>
>
MODBUS_SELECT
>
Serial (➔TCP)
>
Figure 11.4-8 Switch to the Modbus TCP
Communication
Network
Router/
Modem
Ethernet LAN
Device2
(192.168.1.12)
Technical description: Communication modules
- 924 -
1/3
+
+
2
Press
+
set [MOSBUS_SELECT]=TCP
Substation Computer(s) (Master)
TCP master query
Device3
(192.168.1.13)
6F2T0207 (0.01)
Press
ENTER
key
, , , 
to
Message frame
Device X
(192.168.1.XX)
(→p. 645). The use
GRE200 (5,6)