EF_MV (Function ID:441081)
Setting items
EF1-CTFBlk
EF1-UseFor
EF1-ARCBlk
EF2
EF2-Dir
Fwd/
EF2-Angle
Rev
EF2-Vpol
EF2-Timer
DT
EF2
EF2-DPR
TEF2
IEC
EF2
EF2-DPR
EF2-TMS-IEC
TEF2R
UK
EF2
EF2-DPR
EF2-TMS-UK
TEF2R
IEEE
EF2
EF2-DPR
EF2-TMS-
IEEE
EF2-Rtimer
TEF2R
EF2-RTMS-
IEEE
US
EF2
EF2-DPR
EF2-TMS-US
EF4-Rtimer
TEF2R
EF2-RTMS-US
ORG
EF2
EF2-DPR
EF2-TMS-ORG
EF2-Rtimer
TEF2R
EF2-RTMS-
ORG
EF2-k
EF2-a
EF2-c
EF2-kr
EF2-b
Output
EF2-VTFBlk
EF2-CTFBlk
EF2-UseFor
Range
Unit
Non / Block
- EF1 operation block by CTF
Trip / Alarm
- EF1 used for trip or alarm
Non / Block
- Autoreclose block by EF1
NonDir / Forward /
- EF2 directional characteristic
Reverse
-90 - 90
deg EF2 directional characteristic angle
0.5 - 100.0
V EF2 polarizing voltage level
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
IEEE-MI / IEEE-VI /
- EF2 delay type
IEEE-EI / US-CO2 /
US-CO8 / Original
0.02 - 150.00
A EF2 threshold (in DT mode)
10 - 100
% EF2 drop-out/pick-up ratio
0.00 - 300.00
s EF2 operating delay time (in DT mode)
0.02 - 25.00
A EF2 threshold (in IDMT mode)
10 - 100
% EF2 drop-out/pick-up ratio
0.010 - 50.000
- EF2 time multiplier of IEC inverse curve
0.00 - 300.00
s EF2 definite time reset delay
0.02 - 25.00
A EF2 threshold (in IDMT mode)
10 - 100
% EF2 drop-out/pick-up ratio
0.010 - 50.000
- EF2 time multiplier of UK inverse curve
0.00 - 300.00
s EF2 definite time reset delay
0.02 - 25.00
A EF2 threshold (in IDMT mode)
10 - 100
% EF2 drop-out/pick-up ratio
0.010 - 50.000
- EF2 time multiplier of IEEE inverse curve
DEF / DEP
- EF2 reset delay type of IEEE
0.00 - 300.00
s EF2 definite time reset delay
EF2 dependent reset time multiplier of IEEE
0.010 - 50.000
-
inverse curve
0.02 - 25.00
A EF2 threshold (in IDMT mode)
10 - 100
% EF2 drop-out/pick-up ratio
0.010 - 50.000
- EF2 time multiplier of US inverse curve
DEF / DEP
- EF2 reset delay type of US
0.00 - 300.00
s EF2 definite time reset delay
EF2 dependent reset time multiplier of US
0.010 - 50.000
-
inverse curve
0.02 - 25.00
A EF2 threshold (in IDMT mode)
10 - 100
% EF2 drop-out/pick-up ratio
0.010 - 50.000
- EF2 time multiplier of Original inverse curve
DEF / DEP
- EF2 reset delay type of ORG
0.00 - 300.00
s EF2 definite time reset delay
EF2 dependent reset time multiplier of
0.010 - 50.000
-
Original inverse curve
0.00000 - 500.00000
- EF2 user original curve coefficient
0.00000 - 10.00000
- EF2 user original curve coefficient
0.00000 - 10.00000
- EF2 user original curve coefficient
0.00000 - 500.00000
- EF2 user original curve coefficient
0.00000 - 10.00000
- EF2 user original curve coefficient
Non / Block
- EF2 operation block by VTF
Non / Block
- EF2 operation block by CTF
Trip / Alarm
- EF2 used for trip or alarm
- 52 -
Contents
6F2T0207 (0.01)
Default
Note
Non
Trip
Block
NonDir
-45
3.0
DT
0.30
100
1.00
0.30
100
1.000
0.00
0.30
100
1.000
0.00
0.30
100
1.000
DEF
0.00
1.000
0.30.
100
1.000
DEF
0.00
1.000
0.30
100
1.000
DEF
0.00
1.000
0.00000
0.00000
0.00000
0.00000
0.00000
Non
Non
Trip