Discrete 4X Register Bit Data Reporting (26 Registers Defined) - ABB TPU2000 Technical Manual

Modbus/modbus plus/ modbus tcp/ip automation
Table of Contents

Advertisement

TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
41029
Through Fault Counter
41030
Through Fault KSIA
Kiloamps Symmetrical Ia – Current existing
when breaker opened on Phase A.
41031
Through Fault KSIA
Kiloamps Symmetrical Ia – Current existing
when breaker opened on Phase A.
41032
Through Fault KSIB
Kiloamps Symmetrical Ib – Current existing
when breaker opened on Phase B.
41033
Through Fault KSIB
Kiloamps Symmetrical Ib – Current existing
when breaker opened on Phase B.
41034
Through Fault KSIC
Kiloamps Symmetrical Ic – Current existing
when breaker opened on Phase C
41035
Through Fault KSIC
Kiloamps Symmetrical Ic – Current existing
when breaker opened on Phase C
41036
Through Fault Cycle Summation Counter
41037
Through Fault Cycle Summation Counter
41038
Overcurrent Trip Counter
41039
Differential Trip Counter

Discrete 4X Register Bit Data Reporting (26 Registers Defined)

The TPU2000 and TPU2000R offers bit status reporting via 0X and 1X Modbus/Modbus Plus command retrieval.
Some hosts however do not offer the capability to read data via these data types. The data types have been
structured to be reported in 4X data types. Reported data is of the following types:
Logical Outputs
Logical Inputs
Physical Inputs
Forced Physical Input State Reporting
Forced Physical Output State Reporting
Forced Logical Input State Reporting
The following registers only report the status of the elements. Some of the elements are latched and behave as
do their 0X and 1X counterparts. The bits are reset depending upon the reset control via the 4X control registers
(Reference Section 5).
It should be noted that for the following bits, the operational characteristics are included for reference:
TCFA – Trip Circuit Failure Alarm – This bit indicates that the Trip Circuit is Open.
continuously energized (value = 1) until circuit continuity is sensed.
TFA – Trip Failure Alarm – This bit indicates that a fault has not been cleared within the programmable Trip
Failure Time setting of 5 to 60 Cycles. Use the Trip Failure Mode Setting (Differential, Overcurrent, or Differential
and Overcurrent) to select the type of faults for which a trip failure alarm will be given. The Trip Failure Alarm
clears when the current drops below the Trip Failure Drop-Off setting.
PUA - Pick Up Alarm: Differential and Overcurrent (87/51/50/150/46) Pickup Alarm. Indicates that an enabled
protective function is picked up and can be used as a fault detector alarm. The Alarm Resets 500 mS after the
"picked up" state has dropped out.
0<=Range<= 9999
Unsigned Integer 16 Bits
Signed 32 Bit High Order Word MSW
Signed 32 Bit Low Order Word LSW
Signed 32 Bit High Order Word MSW
Signed 32 Bit Low Order Word LSW
Signed 32 Bit High Order Word MSW
Signed 32 Bit Low Order Word LSW
Signed 32 Bit High Order Word MSW
Signed 32 Bit Low Order Word LSW
Unsigned 16 Bit
0 – 9999
Unsigned 16 Bit
0 – 9999
The Alarm remains
104