Table 5-68. Alt 1 Settings Register Definition - ABB TPU2000 Technical Manual

Modbus/modbus plus/ modbus tcp/ip automation
Table of Contents

Advertisement

TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
Register
Address
63235
150G-3 Time Delay
63236
Disturb 3 Pickup X
63237
Level Detector-1 Pickup X

Table 5-68. Alt 1 Settings Register Definition

Register
Address
61152
SPARE_1
61153
Execute Register
0 = No Action
1 = Update Registers
2 = Refresh Registers
61154
Access Password
61155
Access Password
61156
SPARE_2
61157
87T Curve Type
61158
87T Minimum I Operate
61159
87T Percent Restraint
61160
87T Restraint Mode
nd
61161
87T 2
th
61162
87T 5
61163
87T All Harmonic Restraint
61164
87H Tap X Byte
61165
87T-1 Amp
61166
51P-1 Curve Select (TYPE I )
61167
51P-1 Pickup Amps
61168
51P-1 Time Dial/Time Delay
61169
50P-1 Curve Select Byte (TYPE II)
61170
50P-1 Pickup Amps
61171
50P-1 Time Dial/Time Delay
61172
150P-1 Curve Select
61173
150P-1 Pickup Amps
Item
Item
Harmonic Restraint
Harmonic Restraint
Description
Unsigned 16 Bits
0<=Range<=9.99 * 100
Unsigned Integer 16 Bits
0.5<= Range<=5 *10
Unsigned Integer 16 Bits
0.5<= Range<=20 *10 , 201 = Disable
Description
Unsigned 16 Bits
ASCII – 2 Characters Leftmost Digits
ASCII – 2 Characters Rightmost Digits
Unsigned Integer 16 Bits
Unsigned 16 Bits
0.2 <=Range <=1.0 (X10)
15<=Range<=60
Unsigned Integer 16 Bits
Refer to Mode Selection Table
Unsigned Integer 16 Bits
7.5<=Range<=25 (X10)
Unsigned Integer 16 Bits
15<=Range<=40 (X10)
Unsigned Integer 16 Bits
15<=Range<=40 (X10)
Unsigned Integer 16 Bits
6 <=Range<=20 (X10)
Unsigned Integer 16 Bits
2<=Range<=9 (X10)
0.4<=Range<=1.8 (X50)
Unsigned 16 Bits
Range 0-12 (See Text Above)
Unsigned 16 Bits
1<=Range<= 12 *10
0.2<=Range<=2.4 Amp * 50 (See Note)
Unsigned 16 Bits
1<=Range <=10 (X20) Time Dial
0<=Range<=10 (X20) Time Delay
Unsigned Integer 16 bits
0<=Range<=12 (See Text Above)
Unsigned 16 Bits
0.5<=Range<= 20 *10
Unsigned 16 Bits
Dial *10
Delay * 100
Unsigned Integer 16 bits
See Table Above
Unsigned 16 Bits
0.5<=Range<= 20 *10
198

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tpu2000r

Table of Contents