The Breaker Failed to Trip time register is configured a number representing the number of cycles which the
breaker shall trip. The range is a number from 5 to 60. The amount of time for breaker failed to trip is, of course
dependent upon whether the relay is a 50 or 60 Hz model.
Table 5-52. TPU2000/TPU2000R Bit Control Function Definitions
Register
Item
GROUP VI
41452
Execute Register
0 = No Action
1 = Execute
41453
Password
41454
Password
41455
Spare
41456
Pulse Physical Output Change Mask
Bit 0 Trip(lsb)
Bit 1 Output 1 (Terminals 28,27)
Bit 2 Output 2 (Terminal 26,25)
Bit 3 Output 3 (Terminal 24,23)
Bit 4 Output 4 (Terminal 22,21)
Bit 5 Output 5 (Terminal 19,20)
Bit 6 Output 6 (Terminals 17,18)
Bit 7 Output 7 (TPU2000 ONLY)
Bit 8 Reserved
Bit 9 Reserved
Bit 10 Reserved
Bit 11 Reserved
Bit 12 Reserved
Bit 13 Reserved
Bit 14 Reserved
Bit 15 Reserved (msb)
41457
Pulse Physical Output Change Mask
Bit 0 Trip(lsb)
Bit 1 Output 1 (Terminals 28,27)
Bit 2 Output 2 (Terminal 26,25)
Bit 3 Output 3 (Terminal 24,23)
Bit 4 Output 4 (Terminal 22 21)
Bit 5 Output 5 (Terminal 19,20)
Bit 6 Output 6 (Terminal 17,18)
Bit 7 Output 7 (TPU2000 ONLY)
Bit 8 Reserved
Bit 9 Reserved
Bit 10 Reserved
Bit 11 Reserved
Bit 12 Reserved
Bit 13 Reserved
Bit 14 Reserved
Bit 15 Reserved (msb)
Group IV functions operate as follows and detailed in Example 6:
Register 41456 = Pulse Physical Output Mask - Selects Control for the Function Specified.
Register 41457 = Confirm Pulse Physical Output Mask (Copy of Register 41456).
TPU2000/2000R Modbus/Modbus Plus Automation Guide
Description
Unsigned (16 Bits)
ASCII – 2 Characters Leftmost Digits
ASCII – 2 Characters Rightmost Digits
Unsigned (16 Bits)
1 = Pulse Output 0 = No Control
1 = Pulse Output 0 = No Control
1 = Pulse Output 0 = No Control
1 = Pulse Output 0 = No Control
1 = Pulse Output 0 = No Control
1 = Pulse Output 0 = No Control
1 = Pulse Output 0 = No Control
1 = Pulse Output 0 = No Control
Unsigned (16 Bits)
1 = Pulse Output 0 = No Control
1 = Pulse Output 0 = No Control
1 = Pulse Output 0 = No Control
1 = Pulse Output 0 = No Control
1 = Pulse Output 0 = No Control
1 = Pulse Output 0 = No Control
1 = Pulse Output 0 = No Control
1 = Pulse Output 0 = No Control
157