Group Iii Control Features Explained; Table 5-45. Tpu2000R Bit Control Function Definitions; Figure 5-50. Force Physical Input Example - ABB TPU2000 Technical Manual

Modbus/modbus plus/ modbus tcp/ip automation
Table of Contents

Advertisement

STEP 5 -
Host sends following register contents
to initiate Force Physical Input 4 Normal ( Assumed that
default password of all spaces is active).
41417 = 2020 hex (Password Hi)
41418 = 2020 hex (Password Lo)
41419 = 0
41420 = 0008 hex (Select Bit to Change)
41421 = 0000 hex ( Place Bit in Normal "Unforced" State).
41422 = 0000 hex ( Send State of Force = Don't Care)
IMPLEMENTATION TIP –As is common practice with any control, after a control task has been completed via the
network, the host should query the device to assure that control has been executed.

Group III Control Features Explained

The complimentary control functions are available for forcing the Physical Output contacts located at the back of
the relay. The Physical Output force functions follows that of the Physical Input Force Functionality. There are
three modes which a Physical Output may be placed:
NORMAL – The TPU2000R Physical Output reflects that of the logic configured within the protective
relay
FORCED ON – The TPU2000R Physical Output is energized. The Physical Output status is reported
as a 1. If the point status is viewed via ECP or WinECP, the point will show a forced status
FORCED OFF –TPU2000R Physical Output is de-energized. The Physical Output status is reported
as a 0. If the point status is viewed via ECP or WinECP, the point will show a forced status.
Table 5-45 illustrates the mapping for Physical Output Forcing Capabilities.

Table 5-45. TPU2000R Bit Control Function Definitions

Register
Item
41423
Execute Register
0 = No Action
1 = Execute
41424
Password
41425
Password
41426
Spare
41427
Force Physical Output Change Mask
Bit 0 Trip (Terminal 29,30) (lsb)
Bit 1 Output 1 (Terminal 28,27)
Bit 2 Output 2 (Terminal 26,25)
Bit 3 Output 3 (Terminal 24,23)
Bit 4 Output 4 (Terminal 22 21)
Bit 5 Output 5 (Terminal 19,20)
TPU2000/2000R Modbus/Modbus Plus Automation Guide
EXAMPLE 2 - Force Input 4 to a State of 1 and Then to a Force State of 0, and
Then to a Normal State.
(Reserved)
E C
Command
Sequence Through
Modbus Command 16
Preset Multiple Holding Registers
E C
The Relay Responds
over the network that
the command has been
accepted.
Figure 5-50. Force Physical Input Example (Continued)
GROUP III
STEP 6 -
The host sends the register execute
command to the following address
with the following contents.
41416 = 0001 hex
E C
Command
Sequence Through
Modbus Command 16
Preset Multiple Holding Registers
E C
The relay reports the Input Status of Physical Input 1 to be
that reflected at the Physical Input terminals of the TPU 2000R.
A Modbus response will be returned to the host
indicating that the command has been accepted.
Description
Unsigned (16 Bits)
ASCII – 2 Characters Leftmost Digits
ASCII – 2 Characters Rightmost Digits
Unsigned (16 Bits)
1 = Control Bit State 0 = No Control
1 = Control Bit State 0 = No Control
1 = Control Bit State 0 = No Control
1 = Control Bit State 0 = No Control
1 = Control Bit State 0 = No Control
1 = Control Bit State 0 = No Control
143