Table 5-54. Oscillographic Configuration Registers

Register
63968
Execute Register
63969
Access Password
63970
Access Password
63971
Reserved
63972
Start/Stop Accumulation
63973
Acquisition Format
63974
Trigger Mode
63975
Trigger Position
63976
Trigger Flag
Reserved
63977
Trigger Flag
Reserved
63978
Trigger Flag
Bit 0 = Master Trip (lsb)
Bit 1 = Breaker Open
Bit 2 = WCI
Bit 3 = Reserved
Bit 4 = Reserved
Bit 5 = Reserved
Bit 6 = Reserved
Bit 7 = Reserved
Bit 8 = Reserved
Bit 9 = Reserved
Bit 10 = Reserved
Bit 11 = Reserved
Bit 12 = Reserved
Bit 13 = Reserved
Bit 14 = Reserved
Bit 15 = Reserved
63979
Trigger Flag
Bit 0 = 87T (lsb)
Bit 1 = 87H
Bit 2 = 51P-1
Bit 3 = 51N-1
Bit 4 = 50P-1
Bit 5 = 50N-1
Item
Unsigned Integer 16 Bits
0 = No Action
1 = Transfer Settings
2 = Retrieve Settings
2 Leftmost Digits ASCII
2 Rightmost Digits ASCII
Reserved
Unsigned Integer 16 Bits
0 = Stop
1 = Start
Unsigned Integer 16 Bits
0 = 8 Records Max Storage/8 Cycles/Record
1 = 4 Records Max Storage/16 Cycles/Record
2 = 2 Records Max Storage/32 Cycles/Record
3 = 1 Record Stored/64 Cycles/Record
Unsigned Integer 16 Bits
0 = Normal
1 = Single Shot
2 = Normal/Append Mode
3 = Single Shot/Append Mode
Unsigned Integer 16 Bits
Number of quarter cycles to capture pre-fault.
If 63077 = 0 : 0 <= Trigger <= 32
If 63077 = 1 : 0 <= Trigger <= 64
If 63077 = 2 : 0 <= Trigger <= 128
If 63077 = 3 : 0 <= Trigger <= 256
Unsigned Integer 16 Bits
Set to zero
Unsigned Integer 16 Bits
Set to 0
Unsigned Integer 16 Bits
Start Capture on Master Trip State
Start Capture on Breaker Open
Start Capture on Waveform Capture Initiate
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Unsigned Integer 16 Bits Start Capture on:
3 Phase % Differential Current Control
3 Phase Instantaneous Differential Current Control
Winding 1 Phase Time Overcurrent Control
Winding 1 Neutral Time Overcurrent Control
Winding 1 Phase Instantaneous Overcurrent Control
st
1
Description
Winding 1 Neutral Instantaneous Overcurrent Control
160