TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
12/1
12/2
12/3
13/1
13/2
13/3
14/1
14/2
14/3
15/1
15/2
15/3
16/1
16/2
16/3
17/1
17/2
17/3
18/1
18/2
18/3
5.8 Send First Differential Fault Record ( 3 5 8 )
The Differential Fault Record command returns data in two parts. This command requires a data byte message to indicate
which part of the record is to be returned. If the data message 1/2 = 0, part 1 of the record is returned. If the data message
1/2 = 1, part 2 of the record is returned.
Fault Type
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
Data byte
1/1
1/2
1/3
Msg byte
1/1
1/2
1/3
IresC-2 Angle low byte
2nd Harmonic % A-1 byte (*2)
2nd Harmonic % B-1 byte (*2)
2nd Harmonic % C-1 byte (*2)
2nd Harmonic % A-2 byte (*2)
2nd Harmonic % B-2 byte (*2)
2nd Harmonic % C-2 byte (*2)
5th Harmonic % A-1 byte (*2)
5th Harmonic % B-1 byte (*2)
5th Harmonic % C-1 byte (*2)
5th Harmonic % A-2 byte (*2)
5th Harmonic % B-2 byte (*2)
5th Harmonic % C-2 byte (*2)
All Harmonics % A-1 byte (*2)
All Harmonics % B-1 byte (*2)
All Harmonics % C-1 byte (*2)
All Harmonics % A-2 byte (*2)
All Harmonics % B-2 byte (*2)
All Harmonics % C-2 byte (*2)
Winding 1 Tap (*10)
Winding 2 Tap (*10)
Definitions
87T
87H
51P-1
51N-1
50P-1
50N-1
150P-1
150N-1
46-1
51P-2
51G-2
50P-2
50G-2
150P-2
150G-2
46-2
ECI-1
ECI-2
Thru Flt
Harm Rest
0 = Reserved for Unreported Records
0 = Send part 1 of Record, 1 = Send part 2 of Record
Checksum 1/1 + 1/2
Definition-Part 1 of Record
Relay Status (see command 3 4 1, msg 1/1)
Command + Subcommand = 0x58
Total Number of Messages = 28
296