Table 5-11. Default Scaling And Remapping Register Assignments - ABB TPU2000 Technical Manual

Modbus/modbus plus/ modbus tcp/ip automation
Table of Contents

Advertisement

TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
IF NORMAL SCALING IS SELECTED
EQUATION 8:
Register Value = Source Value / Scale
IF REMAINDER SCALING IS SELECTED
EQUATION 9:
Register Value = Remainder of [Source Value/Scale] (commonly referred to as the modulus
function).
IF BIPOLAR CURRENT IS SELECTED
EQUATION 10:
Register Value = (2
IF BIPOLAR VOLTAGE IS SELECTED
EQUATION 11:
Register Value = (2
IF BIPOLAR POWER IS SELECTED
EQUATION 12:
Register Value = (2
IF UNIPOLAR OR NEGATIVE UNIPOLAR EQUATIONS ARE USED, Then the BIPOLAR equations above are
applicable with the note that,
FOR UNIPOLAR, if the result of the equation (10,11,or 12) is positive, then the register is filled with the value
calculated, else the reported value is 0
FOR NEGATIVE UNIPOLAR, If the result of the equation (10,11, or 12) is negative, then the register is filled with
the absolute value of the equation. If the calculated value is positive in sign, then the reported value is 0.
One should notice that if equations 5, 6, 7, 10, 11,or 12 are used, the SCALE entry shown in Figure 5-12?, refers
to the full scale value referenced in the equations. If equations 8 or 9 are used, the SCALE entry shown in Figure
8-2 refers to the Scale divisor denominator as referenced.
TPU2000 and 2000R User Definable Register Defaults
The TPU2000 and 2000R contains User Definable Register default mappings as shown in Table 5-11 below. It
should be noted that the register shall saturate at the maximum values computed and shown in Table 5-10 above.
The maximum saturation value can be computed to be 2N-1 where N is the register size in bits.

Table 5-11. Default Scaling and Remapping Register Assignments

User Definable
Register Type
Register
1: 40001
Unipolar (16)
2: 40002
Offset Bipolar (12)
3: 40003
Offset Bipolar (12)
4: 40004
Offset Bipolar (12)
5: 40005
Offset Bipolar (12)
6: 40006
Offset Bipolar (12)
7: 40007
Offset Bipolar (12)
8: 40008
Offset Bipolar (12)
9: 40009
Offset Bipolar (12)
10: 10010
Offset Bipolar (12)
11: 40011
Offset Bipolar (12)
12: 40012
Offset Bipolar (12)
N-1
Source Value / [FS
*
N-1
Source Value / [FS
*
N-1
Source Value / [FS
*
Start Register
(Bits)
(Bits/Type)
40129 (16/Unsigned)
40393 (16/Unsigned)
40395 (16/Unsigned)
40397 (16/Unsigned)
40513 (32/Unsigned)
40515 (32/Unsigned)
40517 (32/Unsigned)
40552 (32/Signed)
40554 (32/Signed)
40528 (32/Signed)
40530 (32/Signed)
40532 (32/Signed)
CT Ratio])
*
PT Ratio])
*
CT Ratio
PT Ratio])
*
*
FS or
Scale(Type)
1(Normal)
10 (Current)
10 (Current)
10 (Current)
150 (Voltage)
150 (Voltage)
150 (Voltage)
3000 (Power)
3000 (Power)
1000 (Power)
1000 (Power)
1000 (Power)
Description
Relay Status
Load Current A(Wdg 2)
Load Current B(Wdg 2)
Load Current C(Wdg 2)
Voltage VAN
Voltage VBN
Voltage VCN
3 Phase Watts
3 Phase VARs
Phase A Watts
Phase B Watts
Phase C Watts
82

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for: