ABB TPU2000 Technical Manual page 213

Modbus/modbus plus/ modbus tcp/ip automation
Table of Contents

Advertisement

Register
Address
61282
Access Password
61283
Access Password
61284
SPARE_2
61285
87T Curve Type
61286
87T Minimum I Operate
61287
87T Percent Restraint
61288
87T Restraint Mode
nd
61289
87T 2
Harmonic Restraint
th
61290
87T 5
Harmonic Restraint
61291
87T All Harmonic Restraint
61292
87H Tap X Byte
61293
87T-1 Amp
61294
51P-1 Curve Select (TYPE I)
61295
51P-1 Pickup Amps
61296
51P-1 Time Dial/Time Delay
61297
50P-1 Curve Select Byte (TYPE II)
61298
50P-1 Pickup Amps
61299
50P-1 Time Dial/Time Delay
61300
150P-1 Curve Select
61301
150P-1 Pickup Amps
61302
150P-1 Time Dial
61303
46-1 Curve Select Byte
61304
46-1 Pickup Amps
61305
46-1 Time Dial/Time Delay
61306
51N-1 Curve Select (TYPE II)
61307
51N-1 Pickup Amps
61308
51N-1 Time Dial
TPU2000/2000R Modbus/Modbus Plus Automation Guide
Item
ASCII – 2 Characters Leftmost Digits
ASCII – 2 Characters Rightmost Digits
Unsigned Integer 16 Bits
Unsigned 16 Bits
0.2 <=Range <=1.0 (X10)
15<=Range<=60
Unsigned Integer 16 Bits
Refer to Mode Selection Table
Unsigned Integer 16 Bits
7.5<=Range<=25 (X10)
Unsigned Integer 16 Bits
15<=Range<=40 (X10)
Unsigned Integer 16 Bits
15<=Range<=40 (X10)
Unsigned Integer 16 Bits
6 <=Range<=20 (X10)
Unsigned Integer 16 Bits
2<=Range<=9 (X10)
0.4<=Range<=1.8 (X50)
Unsigned 16 Bits
Range 0-12 (See Text Above)
Unsigned 16 Bits
1<=Range<= 12 *10
0.2<=Range<=2.4 Amp * 50 (See Note)
Unsigned 16 Bits
1<=Range <=10 (X20) Time Dial
0<=Range<=10 (X20) Time Delay
Unsigned Integer 16 bits
0<=Range<=12 (See Text Above)
Unsigned 16 Bits
0.5<=Range<= 20 *10
Unsigned 16 Bits
Dial *10
Delay * 100
Unsigned Integer 16 bits
See Table Above
Unsigned 16 Bits
0.5<=Range<= 20 *10
Unsigned 16 Bits
0<=Range<=9.99 * 100
Unsigned Integer 16 bits
See Table Above
Unsigned 16 Bits
1<=Range<= 12 *10
0.2<=Range<=2.4 Amp * 50 (See Note)
Unsigned 16 Bits
1<=Range<=12 * 10
0.2<=Range<= 0.4 *50
Unsigned 16 Bits
Range 0-12 (See Text Above)
Unsigned 16 Bits
1<=Range<= 12 *10
0.2<=Range<=2.4 Amp * 50 (See Note)
Unsigned 16 Bits
Description
203

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tpu2000r

Table of Contents