ABB TPU2000 Technical Manual page 130

Modbus/modbus plus/ modbus tcp/ip automation
Table of Contents

Advertisement

TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
Register
Address
41740
I 1-2 (Ang) – Positive Sequence
Angle Winding 2
41741
I 2-2 (Ang) – Negative Sequence
Angle Winding 2
41742
Scale - Phase Wdg 1
41743
Scale - Phase Wdg 2
41744
Scale - Neutral Wdg 1
41745
Scale - Neutral Wdg 2
The 3 Winding Differential Fault Register Definition Table follows.
Table 5-34. 3 Winding Differential Fault Record Address Table
Register
Address
42305
Differential 3 Winding Fault Control
Register
1 = First Record
2 = Next Record
3 = Oldest Unreported Record
42306
Parameter Flag
42307
Fault Type Element
42308
Setting At Fault Event
42309
Fault Record Number
Item
Unsigned 16 Bit
Unsigned 16 Bit
Unsigned 16 Bit
Unsigned 16 Bit
Unsigned 16 Bit
Unsigned 16 Bit
Item
Description (Multiplier if any)
Description (Multiplier if any)
Fault Record Control Register
Unsigned 16 Bit
1 = Fill 42306 through 42352 with First Record in Data
Buffer.
2 = Fill 42306 through 42352 with next Record Data
pointed to in buffer.
3 = Fill 42306 through 42352 with the last (oldest
unreported) record of data.
Unsigned Integer 16 Bit
Unsigned 16 Bit
00 = 87T – % Differential Alarm
01 = 87H – High Set Inst. Differential Alarm
02 = 51P-1 – Winding 1 Phase Time Overcurrent
03 = 51P-2 – Winding 2 Phase Time Overcurrent
st
04 = 50P-1 – 1
Winding 1 Phase Inst. Overcurrent
st
05 = 50N-1 – 1
Winding 1 Neutral Inst. Overcurrent
nd
06 = 150P-1 – 2
Winding 1 Phase Inst. Overcurrent
nd
07 = 150N-1 – 2
Winding 1 Neutral Inst. Overcurrent
08 = 46-1 – Neg. Sequence 1 Inst. Time Overcurrent
09 = 51P-2 – Winding 2 Phase Time Overcurrent
10 = 51G-2 – Winding 2 Ground Time Overcurrent
st
11 = 50P-2 – 1
Winding 2 Phase Inst. Overcurrent
st
12 = 50G-2 – 1
Winding 2 Ground Inst. Overcurrent
nd
13 = 150P-2 – 2
Winding 2 Phase Inst. Overcurrent
nd
14 = 150G-2 – 2
Winding 2 Ground Inst. Overcurrent
15 = 46-2 – Neg. Sequence 2 Inst. Time Overcurrent
16 = ECI-1 – Event Capture Initiate 1
17 = ECI-2 – Event Capture Initiate 2
18 = Through Fault
19 = Harmonic Restraint
Unsigned 16 Bit
01 = Primary Settings
02 = Alternate 1 Settings
03 = Alternate 2 Settings
Unsigned 16 Bit
120

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tpu2000r

Table of Contents