Counters; Table 5-74. Counter Register Assignment - ABB TPU2000 Technical Manual

Modbus/modbus plus/ modbus tcp/ip automation
Table of Contents

Advertisement

61438
LCD Contrast Adjust
61439
Relay Password
61440
Relay Password
61441
Test Password
61442
Test Password
61443
Meter Winding Mode
61444
VT Configuration
61445
VT Ratio
The Configuration Files for the 3 Winding TPU2000R is as follows:
Table 5-73. TPU2000/2000R Configuration Setting Register Setting
Register
Item
Address
63584
SPARE_1
63585
Execute Register
0 = No Action
1 = Update Registers
2 = Refresh Registers
63586
Access Password
63587
Access Password
63588
SPARE_2
63589
Winding 3 Phase CT Ratio
63590
Winding 3 Neutral CT Ratio
63591
Winding 3 Ground CT Ratio
63592
Winding 3 CT Configuration
63593
Winding Phase Comp – Windings
1-3

Counters

TPU2000/TPU2000R has the ability to count breaker operations in a variety of modes. The same registers can
be accessed via a Modbus Code 03 (Read Holding Registers). For 4X read access, refer to Table 22. The same
information can be read via the refresh register capability through Register 61922.
Counters, write the value of 0 to Registers 61536 through 61547.
Table 5-74 is common to both the 2 Winding and 3 Winding TPU2000R and TPU2000 (available in 2 Winding
Format Only). Table 5-74 is only available for configuration of the TPU2000R 3 Winding Relay.

Table 5-74. Counter Register Assignment

TPU2000/2000R Modbus/Modbus Plus Automation Guide
3 = 60
Unsigned Integer 16 Bits
0<=Range <= 63
ASCII – 2 Characters Leftmost Digits
ASCII – 2 Characters Rightmost Digits
ASCII – 2 Characters Leftmost Digits
ASCII – 2 Characters Rightmost Digits
Unsigned Integer
0 = Winding 1
1 = Winding 2
2 = Winding 3
Unsigned Integer 16 Bits
0 = 69 V Wye
1 = 120V Wye
2 = 120V Delta
3 = 208 V Delta
Unsigned Integer 16 Bits
1<=Range<=45000
Description
Unsigned 16 Bit
ASCII – 2 Characters Leftmost Digits
ASCII – 2 Characters Rightmost Digits
Unsigned Integer 16 Bits
1<=Range<=4000
Unsigned Integer 16 Bits
1<=Range<=4000
Unsigned Integer 16 Bits
1<=Range<=4000
Unsigned Integer 16 Bits
0 = Wye
1 = Delta, IA-IC
2 = Delta, IA- IB
Unsigned Integer 16 Bits
0<=Range <=330 / 30
To reset the Breaker
209