Ulo Connection Settings And User Names; Table 5-78. Ulo Table Map For Character Name Assignment - ABB TPU2000 Technical Manual

Modbus/modbus plus/ modbus tcp/ip automation
Table of Contents

Advertisement

TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
1 = Update Registers
2 = Refresh Registers
61794
Access Password
61795
Access Password
61796
SPARE_2
61797
Hour
61798
Minute
61799
Second
61800
Day
61801
Month
61802
Year

ULO Connection Settings and User Names

The TPU2000/TPU2000R has internal Soft Bits, which are used for logical boolean programming.
reference the IL bulletin for a more detailed explanation of the use of these bits. One should also realize that
Connected means that the ULO X is logically fed back through the appropriate FBX to the appropriate ULIX,
where X is a number from 1 to 9.
Table 5-78 describes the register designation.
Registers 61924 designate whether the ULO is connected to the corresponding ULI. Registers 61926 through
61958 contain the 8 characters, which make up the ULO Name.

Table 5-78. ULO Table Map For Character Name Assignment

Address
Item
61920
SPARE_1
61921
Execute Register
0 = No Action
1 = Update Registers
2 = Refresh Registers
61922
Access Password
61923
Access Password
61924
SPARE_2
61925
ULO/ULI Connection
Designation
Bit 0 = ULO9
Bit 1 = ULO8
Bit 2 = ULO7
Bit 3 = ULO6
Bit 4 = ULO5
Bit 5 = ULO4
Bit 6 = ULO3
Bit 7 = ULO2
Bit 8 = ULO1
Bit 9 = Reserved
Bit 10 = Reserved
Bit 11 = Reserved
Bit 12 = Reserved
Bit 13 = Reserved
Bit 14 = Reserved
Bit 15 = Reserved
61926
ULO 1 Rightmost 2 Characters
61927
ULO 1 Characters
61928
ULO 1 Characters
61929
ULO 1 Leftmost 2 Characters
ASCII – 2 Characters Leftmost Digits
ASCII – 2 Characters Rightmost Digits
Unsigned 16 Bit Hour Range 0-23
Unsigned 16 Bit Minute Range 0-59
Unsigned 16 Bit Second Range 0-59
Unsigned 16 Bit Day Range 1-31
Unsigned 16 Bit Month Range 1-12
Unsigned 16 Bit Year Range 00-99
Description
Unsigned 16 Bits
ASCII – 2 Characters Leftmost Digits
ASCII – 2 Characters Rightmost Digits
Unsigned Integer 16 Bit
0 = Connected 1 = Not Con.
0 = Connected 1 = Not Con.
0 = Connected 1 = Not Con.
0 = Connected 1 = Not Con.
0 = Connected 1 = Not Con.
0 = Connected 1 = Not Con.
0 = Connected 1 = Not Con.
0 = Connected 1 = Not Con.
0 = Connected 1 = Not Con.
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
2 Digit ASCII Characters
2 Digit ASCII Characters
2 Digit ASCII Characters
2 Digit ASCII Characters
Please
212

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for: